Laserfiche WebLink
Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Date: <br />April 25, 2023 <br /> Facility Address: <br /> 420 W YOSEMITE AVE, MANTECA <br /> Facility Name: <br /> SAVE ON FUEL <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br /> 208 CCR 2716(a-e) Failure to comply with the designated operator inspection requirements. <br />OBSERVATION: The designated operator failed to note the correct test dates for the secondary containment on <br />the designated operator inspection reports. The incorrect date is 02/04/2021. The correct date for the secondary <br />containment is 8/11/2021. <br />REGULATION GUIDANCE: During the inspection, the designated operator shall check that all required testing and <br />maintenance for the UST system have been completed and document the dates they were done. <br />CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br />the required information on the reports. <br />This is a repeat violation, Class II. <br /> 319 CCR 2635, 2637.2, 2665, 2712 Failure to comply with overfill prevention equipment requirements. <br />OBSERVATION: The 87 Overfill prevention equipment testing has not been conducted. This testing was due by <br />9/2021, testing is 19 months past due. <br />REGULATION GUIDANCE: Overfill prevention equipment inspections were required to be conducted by October <br />13, 2018, and every 36 months thereafter, and within 30 days of completion of a repair. <br />CORRECTIVE ACTION: Immediately schedule this test and provide 48 hours notification to the EHD. <br />This is a repeat violation, Class II. <br />Overall Inspection Comments: <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, by 05/25/2023. <br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br />of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br />($156). To schedule an appointment, please call (209) 468-3420. <br />AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br />THIS FACILITY BACK INTO COMPLIANCE. <br />THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Inspector Phone: <br /> PAUL NSO, EH Specialist <br /> Inspector:April 25, 2023 Date: <br />Printed Name and Title: <br />E mail report to:Jatin Aneja, Operator. <br />(209) 616-3049 <br />FA0001196 PR0231458 SC001 04/25/2023 <br />EHD 23-01 Rev. 12/06/2021 Underground Storage Tank Program OIRPage 7 of 7 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD