Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> FLAG CITY CHEVRON 6421 CAPITOL AVE, LODI April 27, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 122 CCR 2712(f)Failure to implement corrections and submit written response within 30 days of receiving the report. <br /> OBSERVATION:An inspection was last done on 4/19/2022 (amended on 5/2/2022)and an inspection report was <br /> issued identifying information to be submitted to bring this site into compliance. This information was required to be <br /> submitted by 6/1/2022. This information was received on 6/15/2022, 14 days late. <br /> REGULATION GUIDANCE:An operator that receives an inspection report shall have 30 days to implement the <br /> corrections specified in the inspection report and comply with permit conditions. The corrective action shall include <br /> all of the recommendations made in the report. The operator shall submit a written response that includes a <br /> statement documenting corrective actions taken or proposing corrective actions which will be taken. <br /> CORRECTIVE ACTION: Ensure that a written response documenting corrective actions taken or proposed is <br /> submitted and all corrections implemented within 30 days of receiving an inspection report. <br /> This is a repeat violation, Class ll. <br /> 302 CCR 2630(d), 2641(a)Leak detection equipment not installed/maintained/located to detect leaks at earliest <br /> opportunity. <br /> OBSERVATION: The 87 siphon sensor was found slanted and not located at the bottom of the sump to detect a <br /> leak at the earliest opportunity. <br /> REGULATION GUIDANCE: Monitoring equipment shall be maintained to be able to detect a leak at the earliest <br /> possible opportunity. <br /> CORRECTIVE ACTION: The sensor was relocated to the lowest point of the sump by the service technician. <br /> Ensure that all monitoring equipment is maintained to detect a leak at the earliest opportunity. <br /> This was corrected on site. <br /> This is a repeat violation, Class ll. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 5/27/2023. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($156). To schedule an appointment, please call (209)468-3420. <br /> FA0000485 PR0231706 SCO01 04/27/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />