Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by Manufacturer ❑✓ Industry Standard Professional Engineer <br /> Test Type Pressure Ll Vacuum ZHydrostatic <br /> Test Equipment Used:Ts-STS <br /> Sump/UDC ID 1/2 3/4 5/6 7/8 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 36" 36" 36" 36" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 12-1 12" 12" 12" <br /> (inches) <br /> Test Start Time 9:55AM 9:55AM 11:07AM 11:07AM <br /> Initial Reading 3.3384" 6.6107" 1.0759" 4.4781" <br /> Test End Time 10:10AM 10:10AM 11:22AM 11:22AM <br /> Final Reading 3.3377" 6.6107" 1.0756" 4.4781" <br /> Change in Reading 0.000711 oil 0.0003 oil <br /> Pass/Fail Criteria +/- 0.00211 +/- 0.0021, +/- 0.00211 +/- 0.00211 <br /> Tightness Test Results Pass Fail ✓ Pass Fail Z Pass Fail Pass Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass Fail Criteria <br /> Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />