Laserfiche WebLink
SAN J O A R N Environmental Health Department <br /> -:a U ;� i _# �V AMENDED <br /> 5/9/2023 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> SINCLAIR NORTH MAIN 1 1245 N MAIN ST, MANTECA May 08, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 305 HSC 25290.1,25290.2, 25291 Failed to maintain secondary containment(e.g.failure of secondary containment <br /> testing). <br /> OBSERVATION: Loss of brine was found in the UDC 5/6 indicating a leak in the secondary containment. <br /> REGULATION GUIDANCE: Secondary containment shall be impervious to the liquid and vapor of the substance <br /> contained and constructed to prevent structural weakening as a result of contact with any hazardous substances <br /> released from the primary containment. <br /> CORRECTIVE ACTION: Immediately contact a properly licensed,trained, and certified contractor to make repairs <br /> to the UST system under permit and inspection of the EHD. <br /> This is a Class II violation. <br /> 307 HSC 25290.1(c3), 25290.2(c3) Failure to keep water out of the secondary containment system (post-Jul 2003). <br /> OBSERVATION:Water was found in the 87 and 91 fill sumps, 87, 91,diesel spill containers, 87 and diesel STP <br /> sumps. <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION: The service technician removed 17 gallons of liquid from the 87 and 91 fill sumps, 87, 91, <br /> diesel spill containers, 87 and diesel STP sumps and returned the sensor to its proper location. Immediately contact <br /> a properly licensed,trained, and certified contractor to address the water intrusion into the 87 and 91 fill sumps, 87, <br /> 91, diesel spill containers, 87 and diesel STP sumps under permit and inspection of the EHD. <br /> This is a minor violation. <br /> 318 CCR 2635, 2637.1,2665, 2712 Failed to meet spill container requirements. <br /> OBSERVATION: The 87, 91 and diesel spill container failed to have a minimum capacity of five gallons because <br /> liquid was found in the containers. <br /> REGULATION GUIDANCE:All spill containers shall have a minimum capacity of five gallons. <br /> CORRECTIVE ACTION: The service technician removed the liquid that was found in the containers. <br /> This was corrected on site. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> An inspection report was provided to the facility operator on the day of inspection. The report was amended <br /> and replaces the initial report. <br /> *Added Violation#101 and 206. <br /> FA0024040 PR0541906 SCO01 05/08/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 7 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />