Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2360225 Date: 6/5/2023 <br /> Site Name/ID. 7-ELEVEN 41216/41216 <br /> Address: 770 W.Charter Way <br /> City: Stockton State: CA Zip: 95206 <br /> Tank ID Rul Prem Dsl <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 2 4 4 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. unknown unknown unknown <br /> Pump Operating Pressure(psi) 30.00 32.00 32.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 30.00 32.00 32.00 <br /> NIA for Electronic Lo's <br /> Resiliency(ml) 125.00 120.00 110.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 17 17 18 <br /> NIA for Electronic Lo's <br /> Opening Time(sec) 3 2 3 <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: Expire Date: 11/7/2024 <br /> Environmental Compliance for Petroleum Systems <br /> ©2023 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />