Laserfiche WebLink
<br /> <br /> <br /> made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 4 of 5 <br />Test Method Developed by Manufacturer Industry Standard Professional Engineer <br />Test Type Pressure Vacuum Hydrostatic <br />Test Equipment Used: Caldwell Level Change Indicator <br />Sump/UDC ID UDC 9&10 UDC 11&12 <br />Sump Manufacturer Western FG Western FG <br />Sump Depth (inches) 24" 25" <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />11" 9 1/2" <br />Test Start Time 11:32 11:37 <br />Initial Reading .001 .001 <br />Test End Time 12:02 12:07 <br />Final Reading .001 .001 <br />Change in Reading 0 0 <br />Pass/Fail Criteria > .002 > .002 <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Sump/UDC ID 1-Diesel-FS 2-91-FS 3-87-FS <br />Sump Manufacturer XERXES XERXES XERXES <br />Sump Depth (inches) 71" 72" 67" <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />21" 23" 19" <br />Test Start Time 11:22 11:27 10:37 <br />Initial Reading .001 .001 .001 <br />Test End Time 11:52 11:57 11:07 <br />Final Reading .001 .001 .001 <br />Change in Reading 0 0 0 <br />Pass/Fail Criteria > .002 > .002 > .002 <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Additional copies of this page may be attached. <br /> <br />8. SUMP/UDC TEST (continued)