My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2023
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
E
>
EL DORADO
>
713
>
2300 - Underground Storage Tank Program
>
PR0521604
>
COMPLIANCE INFO_2023
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
9/11/2023 12:33:31 PM
Creation date
4/26/2023 3:21:41 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2023
RECORD_ID
PR0521604
PE
2371
FACILITY_ID
FA0014678
FACILITY_NAME
NATIONAL PETROLEUM
STREET_NUMBER
713
Direction
N
STREET_NAME
EL DORADO
STREET_TYPE
ST
City
STOCKTON
Zip
95202
APN
13905214
CURRENT_STATUS
01
SITE_LOCATION
713 N EL DORADO ST
P_LOCATION
01
P_DISTRICT
001
QC Status
Approved
Scanner
SJGOV\kblackwell
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
21
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Date: <br />May 30, 2023 <br /> Facility Address: <br /> 713 N EL DORADO ST, STOCKTON <br /> Facility Name: <br /> NATIONAL PETROLEUM <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br /> 307 HSC 25290.1(c3), 25290.2(c3) Failure to keep water out of the secondary containment system (post-Jul 2003). <br />OBSERVATION: Water was found in the UDC 1/2, 3/4, 5/6, 7/8, 11/12, vent, 87 and diesel fill sumps. <br />REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br />system by precipitation, infiltration, or surface runoff. <br />CORRECTIVE ACTION: The service technician removed approximately 12 gallon of liquid from the UDC 1/2, 3/4, <br />5/6, 7/8, 11/12, vent, 87 and diesel fill sumps and returned the sensor to its proper location. Immediately contact a <br />properly licensed, trained, and certified contractor to address the water intrusion into the UDC 1/2, 3/4, 5/6, 7/8, <br />11/12, vent, 87 and diesel fill sumps under permit and inspection of the EHD. <br />This was corrected on site. <br />This is a minor violation. <br /> 312 HSC 25290.2(d) Monitoring system incapable of detecting entry into secondary containment (Jul 2003-Jun 2004). <br />OBSERVATION: The 91 STP sensor failed when tested. <br />REGULATION GUIDANCE: The continuous monitoring system shall be maintained to detect the entry of the liquid <br />or vapor phase of the hazardous substance stored in the primary containment into the secondary containment and <br />to detect water intrusion into the secondary containment. <br />CORRECTIVE ACTION: The sensor was replaced and retested during the inspection. <br />This was corrected on site. <br />This is a repeat violation, Class II. <br />Overall Inspection Comments: <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, by 06/29/2023 . <br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br />of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br />($156). To schedule an appointment, please call (209) 468-3420. <br />AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br />THIS FACILITY BACK INTO COMPLIANCE. <br />THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Inspector Phone: <br /> PAUL NSO, EH Specialist <br /> Inspector:May 30, 2023 Date: <br />Printed Name and Title: <br />E mail report to:Abdo Nashir, Environmental Contact. <br />(209) 616-3049 <br />FA0014678 PR0521604 SC001 05/30/2023 <br />EHD 23-01 Rev. 12/06/2021 Underground Storage Tank Program OIRPage 6 of 6 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD
The URL can be used to link to this page
Your browser does not support the video tag.