Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for ARCO AMPM as of April 20, 2023. <br /> Open violations from June 27, 2022 inspection <br /> Violation#305-Failed to maintain secondary containment(e.g.failure of secondary containment testing). <br /> OBSERVATION: Brine was observed in the diesel fill sump indicating a leak in the secondary containment. <br /> REGULATION GUIDANCE: Secondary containment shall be impervious to the liquid and vapor of the substance <br /> contained and constructed to prevent structural weakening as a result of contact with any hazardous substances <br /> released from the primary containment. <br /> CORRECTIVE ACTION: Immediately contact a properly licensed,trained, and certified contractor to make repairs <br /> to the UST system under permit and inspection of the EHD. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Violation#307-Failure to keep water out of the secondary containment system(post-Jul 2003). <br /> OBSERVATION: Liquid was observed in the diesel STP sump. <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION: The service technician removed approximately 1 cup of liquid from the diesel STP sump <br /> and returned the sensor to its proper location. Immediately contact a properly licensed,trained, and certified <br /> contractor to address the water intrusion into the diesel STP sump under permit and inspection of the EHD. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Page 1 of 1 <br />