Laserfiche WebLink
SAN J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Harney Lane 76 1 141 E HARNEY LN, LODI July 12, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 203 CCR 2712(b)(1-2)Failure to maintain monitoring records for 36 months and maintenance records for 60 months. <br /> OBSERVATION: Monitoring records for the last three years were not found on site. The following test results were <br /> missing: <br /> -2020, 2021, 2022 monitoring system certification <br /> -02/28/2022 overfill prevention inspection <br /> REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1)date and time of all monitoring or sampling; (2)monitoring equipment calibration and maintenance <br /> records; (3)results of any visual observations; (4)results of sample analysis performed a lab or in the field; (5)logs <br /> of all readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6)results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the <br /> last three years on site. <br /> This is a repeat violation, Class II. <br /> 208 CCR 2716(a-e) Failure to comply with the designated operator inspection requirements. <br /> OBSERVATION: The following issues were observed on the monthly designated operator inspection reports: <br /> -The designated operator failed to check and note the correct test dates for the 07/2022 through 06/2023 <br /> designated operator inspection reports. <br /> -The 10/2/22 and 11/22/22 inspections were completed late <br /> -The 07/27/22 and 11/22/22 reports were missing the date the report was provided to the owner and were not <br /> signed by the owner/operator <br /> -The 10/2/22 report did not address the 09/02/22 alarms <br /> -The owner did not provide follow-up actions on the 12/22/22 report <br /> REGULATORY GUIDANCE:The designated operator visual inspections shall be conducted within 30 days or less <br /> of the previous inspection. During the inspection,the designated operator shall check that all required testing and <br /> maintenance for the UST system have been completed and document the dates they were done. Within 48 hours <br /> of the completion of the designated UST operator visual inspection,the designated operator shall sign and provide <br /> the owner or operator with a copy of the inspection report. Within 72 hours of being provided a signed copy of the <br /> report,the owner or operator shall provide a description of each corrective action taken or to be taken and shall sign <br /> and date the report, acknowledging the identified compliance issues. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br /> the required information on the reports. The designated operator visual inspections shall be conducted within 30 <br /> days or less of the previous inspection. Ensure all designated operator inspection reports are completed and signed <br /> within the required time frame in the future. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> FA0024750 PR0543574 SCO01 07/12/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 6 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />