Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for TIGER EXPRESS STORES as of August 30, 2023. <br /> Open violations from June 20, 2023 inspection <br /> Violation#118-Failure to submit the"Overfill Prevention Equipment Inspection Report Form"within 30 <br /> days. <br /> OBSERVATION: An overfill prevention equipment inspection was performed on 12/21/2022(diesel drop tube).A <br /> test report has not been submitted to the EHD or the California Environmental Reporting System(CERS). <br /> REGULATION GUIDANCE:A copy of the inspection report form must be submitted within 30 days of the test. <br /> CORRECTIVE ACTION: Immediately provide this report to the EHD. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> �ISupporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> O� 'L,• 1�. C�^n\�� LA '� c1 C o� awn c), <br /> • .1. o�..r� �3�,,;,,, No holo. &. �. - <br /> ham 6, -",& 4- -�I�o u A,h <br /> Violation#203-Failure to maintain monitoring records for 36 months and maintenance records for 60 <br /> months. <br /> OBSERVATION: Maintenance and monitoring records for the last three years were not found on site. <br /> -The 6/3/2021 overfill prevention equipment test reults were not found on site during the inspection. <br /> REGULATION GUIDANCE:These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1)date and time of all monitoring or sampling; (2)monitoring equipment calibration and maintenance <br /> records; (3)results of any visual observations; (4)results of sample analysis performed a lab or in the field;(5)logs <br /> of all readings of gauges or other monitoring equipment,ground water elevations,or other test results; (6)results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the <br /> last three years on site. Submit copies of any missing work orders and alarm records to the EHD. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: S S kp W <br /> , w Q s CJIL4 <br /> 0.�W 0.0 C `ice�y <br /> Page 1 of 2 <br />