Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> H&M- BW#98 2501 JACKSON AVE, ESCALON July 19, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 214 CCR 2712 Failure to comply with UST operating permit conditions. <br /> OBSERVATION: The VMI leak detector was replaced with a Red Jacket and a permit was not obtained from the <br /> EHD. <br /> REGULATION GUIDANCE: Emergency repairs relating to UST system monitoring and release detection may be <br /> performed by a properly licensed,trained, and certified contractor pursuant to the EHD's policy and a permit <br /> obtained within one business day from the EHD. All other repairs must have a permit submitted to and approved by <br /> the EHD prior to beginning work. <br /> CORRECTIVE ACTION: Immediately obtain a permit from the EHD for the VMI replacement. A"Failure to Obtain a <br /> Permit"penalty applies. <br /> This is a minor violation. <br /> 308 CCR 2632(c), 2634(d), 2636(f) Failure of the leak detection equipment to have an audible and visual alarm. <br /> OBSERVATION: The float and chains in the 1-2 UDC failed to stop the flow of product at the dispenser when <br /> tested. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor replace <br /> the failed component with a functional component(LG 113-x listed, if applicable), and obtain a permit within one <br /> business day from the EHD, if needed. If the failed component can't be replaced immediately,there is a possibility <br /> that the 87 UST system may be red tagged to prevent fuel inputs. <br /> This is a repeat violation, Class II. <br /> 318 CCR 2635, 2637.1,2665, 2712 Failed to meet spill container requirements. <br /> OBSERVATION: The 91 premium direct-bury spill container failed when tested. <br /> REGULATION GUIDANCE:All spill containers shall have a minimum capacity of five gallons and be capable of <br /> containing a spill or overfill until it is detected or cleaned up. <br /> CORRECTIVE ACTION: Immediately discontinue deposition of petroleum into this tank until the component is <br /> repaired or replaced by a properly licensed, trained, and certified contractor under permit and inspection of the EHD. <br /> If the spill container can't be replaced immediately,there is a possibility that the 91 premium UST system may be <br /> red tagged to prevent fuel inputs. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 8/18/2023. <br /> FA0003910 PR0231488 SCO01 07/19/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />