My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2023
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
S
>
STIMSON
>
2000
>
2300 - Underground Storage Tank Program
>
PR0231732
>
COMPLIANCE INFO_2023
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
4/10/2024 8:47:03 AM
Creation date
7/7/2023 8:57:39 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2023
RECORD_ID
PR0231732
PE
2361
FACILITY_ID
FA0003648
FACILITY_NAME
STKN ARMY AVIATION SUPP FACILITY*
STREET_NUMBER
2000
STREET_NAME
STIMSON
STREET_TYPE
RD
City
STOCKTON
Zip
95206
APN
17726004
CURRENT_STATUS
01
SITE_LOCATION
2000 STIMSON RD
P_LOCATION
99
P_DISTRICT
001
QC Status
Approved
Scanner
SJGOV\lsauers1
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
45
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by © Manufacturer F Industry Standard āIā Professional Engineer <br /> Test Type © Pressure E Vacuum Ir Hydrostatic <br /> Test Equipment Used: Incon TS-STS Sump Test System <br /> Sump/UDC ID UST STP Reel UDC Transition Sump <br /> Sump Manufacturer Containment Solutions Containment Solutions Western Fiberglass <br /> Sump Depth (inches) 32 36 48 <br /> Sump Bottom to Top of 18 16 32 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 1044 1044 1044 <br /> Initial Reading 7.5098 5.7213 3.3910 <br /> Test End Time 1059 1059 1059 <br /> Final Reading 7.5096 5.7213 3.3905 <br /> Change in Reading 0.0002 0 0.0005 <br /> Pass/Fail Criteria +/-0.002" +/-0.002" +/-0.002" <br /> Tightness Test Results Pass Fail Q Pass Fail E Pass © Fail 0 Pass © Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results © Pass © Fail Pass 0 Fail r] Pass © Fail I! Pass Ll Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail' and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />
The URL can be used to link to this page
Your browser does not support the video tag.