Laserfiche WebLink
JONES COVEY GROUP, INC. <br /> COMPLETE FUEL SYSTEM CONSTRUCTION EL MAINTENANCE SERVICES <br /> MECHANICAL / ELECTRONIC LEAK DETECTOR CERTIFICATION <br /> SITE: Pilot 1017 Lathrop DATE: 1 1 09 2 0 2 3 <br /> State Facility# CONTACT: Manager <br /> 1017 PHONE: (209)982-1450 <br /> JOB#: 2368215-1-2 <br /> Tank # Tank1 <br /> Product 87 Unleaded <br /> LD Manufacturer VMI <br /> LD Model 99 LD-2000 <br /> Sump Condition Good <br /> Operation Pressure 29 PSI <br /> PSI <br /> Opening Time(Sec) 12 Seconds <br /> Metering Pressure <br /> 17 PSI <br /> (PSI) <br /> Functional Element <br /> Holding Pressure 25 PSI <br /> Leak Rate LD Detected <br /> (GPH) 3 GPH <br /> Does LD Detect 3 GPH Yes <br /> Leak Rate? <br /> LD Serial 17051150 <br /> Comments: <br /> Technician Justin Zorn License Number VMI -#4634 <br /> Signature <br /> 9595 LUCAS RANCH ROAD, RANCHO CUCAMONGA,CA 91730- LICENSED IN 41 STATES <br /> California State License#804431 A, B, HAZ <br />