Laserfiche WebLink
JONES COVEY GROUP, INC. <br /> WMPLETE FUEL SYSTEM CONSTRUCTION fit MAINTENANCE SERVICES <br /> Line Tightness Test <br /> SITE: Pilot 1017 Lathrop DATE: 1 0 04 2 0 2 2 <br /> Site Address# CONTACT: Site Manager 0 <br /> 345 Roth Rd., Lathrop CA 95231 PHONE: 209 982-1460 <br /> JOB#: 2249279-1-3 <br /> Test Number 1 <br /> Sump Pump# 1 <br /> Product 87 Unleaded <br /> Piping Type Fiberglass <br /> Piping Manufacturer NOV-Smith <br /> Turbine Manufacturer Red-Jacket <br /> Isolation (pump) Function Element <br /> Isolation (disp.) Shear Valve <br /> Line Pressure 35 psi <br /> Initial Pressure Test 35 psi <br /> Final Pressure Test 35 psi <br /> Begin Time 1:45pm <br /> End Time 2:15pm <br /> Change In Time 30 Minutes <br /> Change In Pressure 0 psi <br /> Leak Rate 0 psi <br /> Pass/Fail Pass <br /> Line Test Method VMI-Pressure test <br /> Comments: <br /> Technician:lssac Garcia License Number VMI Cert#3363 <br /> Signature ?yyaG �01-a <br /> 9595 LUCAS RANCH ROAD, RANCHO CUCAMONGA CA 91730- LICENSED IN 41 STATES <br /> California State License#804431 A, B HAZ <br />