Laserfiche WebLink
_ anknology LDT 5000 Field Test Apparatus Page 1 of 1 <br /> TLine Leak Detector Test <br /> Work Order: 2362074 Date: 9/21/2023 <br /> Site Name/ID. 7-ELEVEN 14113, MKT 2368/14113 <br /> Address: 3040 BENJAMIN HOLT DR @ GRIGSBY <br /> City: STOCKTON State: CA Zip: 95219 <br /> TanklD 87 87 91 <br /> Product REGULAR REGULAR SUPREME <br /> Product Line 1 1 1 <br /> Tested From 3 3 3 <br /> Existing/New Existing Replacement Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. 09081368 23031056 09071276 <br /> Pump Operating Pressure(psi) 30.00 30.00 29.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 27.00 27.00 25.00 <br /> NIA for Electronic Lo's <br /> Resiliency(ml) 125.00 125.00 110.00 <br /> NIA for Electronic Lo's <br /> Metering PSI x 17 17 <br /> NIA for Electronic Lo's <br /> Opening Time(sec) x 4 5 <br /> NIA for Electronic Lo's <br /> Test Results Fail Pass Pass <br /> Technician Comments:87 leak detector failed. replaced and tested new LD with passing results <br /> Technician Name: Clint Fuhrman Certification#: 96737 <br /> Technician Signature: 7�/, .. Expire Date: 2/2/2025 <br /> Environmental Compliance for Petroleum Systems <br /> ©2023 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />