TAI T <br /> Test Date: 09/21/2023 <br /> LEAK DETECTOR TESTING <br /> Facility ID: PGE095 Client Name: PACIFIC GAS AND ELECTRIC <br /> Street Address: 4040 WEST LN. Technician: Jaime Jaurequi <br /> City: STOCKTON ICC#: 8340695 <br /> Zip Code/State: 95204 / CA Manufacturer Cert#: B48138-4282 VMI <br /> Test Information <br /> Product Unleaded Diesel <br /> Manufacturer Veeder-Root Veeder-Root <br /> Model 8484 8484 <br /> New Leak Detector No No <br /> Yes/No <br /> Serial Number 119293 119295 <br /> Electronic LD Yes Yes <br /> Yes/No <br /> Calibrated Test Leak <br /> Rate: (189 mil/min Yes Yes <br /> 10 PSI) (Yes/No <br /> Check Valve Holding 28psi 28psi <br /> PSI <br /> Resiliency N/A N/A <br /> (Bleed Back MIL) <br /> Slow Flow N/A N/A <br /> Metering PSI / N/A <br /> Turbine Shut Down <br /> Electronic LD Yes Yes <br /> Yes/No/NA <br /> Slow Flow At Nozzle N/A N/A <br /> Yes/No/NA <br /> Opening Time N/A N/A <br /> (Seconds) <br /> Pass/Fail Pass Pass <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The leak detector test pass/fail is determined using a low flow threshold trip <br /> rate of 3 gph at 10 PSI. <br /> Technician Signature: Date: 09/21/2023 <br /> CA NO 588098 1 AZ IicN 095984 1 NV Hc#0049666 r TX HO CR0000041 <br />