2 <br /> <br /> <br />E-mailed Sammy Orlando <sam@orlandosmarket.com> and Kurt <kurt@k12architects.com> requesting for the following <br />information: <br />1. Section G: Choose one of the following methods. Needs to be checked. <br />2. Missing Manufacture cut sheets for piping, tanks, and equipment e.g. monitoring equipment, overspill <br />containment device, overfill protection device, dispenser pan, etc. <br />3. One ICC Installer with all Manufacture Certifications: tanks, piping, flex connectors, fill/STP sumps, UDCs, Vent <br />Sumps, Penetrations, Spill Buckets <br />4. One ICC Technician with all manufacture certification for leak detectors, overfill, panel/sensors, <br />5. Diagram of vacuum monitoring <br />6. Map of wells, sewer, and storm drains, <br />7. Provide the length of the longest piping run <br />8. Ground water level <br />9. ELD Workplan <br />10. Buoyancy calculation does not have an engineer wet stamp <br />11. Provide the longest pipe length <br /> <br /> <br /> <br /> <br />Stacy Rivera <br />Lead Sr. Registered Environmental Health Specialist <br /> <br />San Joaquin County Environmental Health Department <br />1868 E. Hazelton Ave., Stockton, CA 95205 <br />phone (209) 616-3043 <br />fax (209) 468-3433 <br /> <br /> <br />*Test notifications and test results should be sent to the general UST email: ust@sjgov.org* <br /> <br />*NOTE* I will be out of office every other Friday. If you are unable to reach me on those days and need to speak to someone <br />immediately, please call (209) 468-3420 or email our UST email address. <br />December 9, 23 | January 6, 20 | February 3, 17 | March 3, 17, 31 <br /> <br />EHD will be closed for the holidays on: <br />December 26 | January 2, 16 | February 20 | May 29 <br />