Laserfiche WebLink
Precision Line Tightness Test <br /> Data Chart for use with Petro Tite <br /> Facility: George Kishida Test Date: 11/16/2023 <br /> Address: 1725 Ackerman Dr Test Com an : B.Z.Service Station Maintenance i <br /> Ci : Lodi Address: 1041 Triangle Ct,West Sac,CA 95605 <br /> County: San Joaquin EMD <br /> Conducted by: Rhome Desbiens Signature: <br /> License#: 04-1691 <br /> Petro Tite#: 3000010369 <br /> Is a tank test to be made with this line test? E]Yes®No � <br /> Make and a of um or dispensers Suction or Submersible): Tokheim Submersible <br /> Weather: partlycloud Tem in Tanks: *F *C � <br /> Cover over lines: concrete Burial Depth: 5' <br /> Pressure Volume ] Remarks: Size, <br /> Identify Time Log of test Net length,&type of <br /> each line procedures,Ambient Psi or kpa Reading <br /> (Military) Change line,Flex <br /> as tested Temp,Weather,Etc Before After connectors,Repairs <br /> Before After Before After <br /> DSL 1 1118 Start Line Test�L� 50 <br /> DSL 1 1128 Continue Line Test 49 50 .0660 .0660 .0000 . _ _. <br /> DSL 1 1138 Continue Line Test 50 50 .0660 .0660 .0000 F _ <br /> DSL 1 1148 Continue Line Test 50 50 .0660 .0660 .0000 <br /> � fDSL 1 1158 Continue Line Test 50 50 .0660 0660 .0000 r —^— <br /> .._ ���L��UC _..__................_.......... -- <br /> _.__.._._._. _..... ............. <br /> DSL l 1208 Continue Line Test 50 50 .0660 .0660 0000 Line Test Pass—ed-� <br /> DSL 2 1219 Start Line Test - 50 .0800 2" FG 30' <br /> DSL 2 1229 Continue Line Test 50 50 .0800 .0800 .0000 _ <br /> DSL 2 1239 Continue Line Test F50 50 .0800 .0800 .0000 <br /> DSL 2 1249 Continue Line Test 50 50 IF .0800 .0800 .0000 <br /> DSL 2 1259 Continue Line Test 50 50 .0800 .0800 .0000 Line Test Passed <br /> C �� � CL1��C_�C=�C <br />