Laserfiche WebLink
Precision Line Tightness Test <br /> Data Chart for use with Petro Tite <br /> Facili : George Kishida Test Date: 11/16/2023 <br /> Address: 1725 Ackerman Dr Test Com an : B.Z. Service Station Maintenance <br /> City: Lodi Address: 1041 Triangle Ct, West Sac,CA 95605 <br /> County: San Joaquin EMD <br /> Conducted by: Rhome Desbiens Signature: <br /> License#: 04-1691 <br /> Petro Tite#: 3000010369 <br /> r[Make <br /> tank test to be made with this line test? �O Yes®No <br /> and type of pump or dispensers(Suction or Submersible): Tokheim Submersible <br /> ather: artl cloud Tem in Tanks: *F *C <br /> ver over lines: concrete Burial Depth: 5' <br /> [::Pressure Volume Remarks: Size, <br /> Time <br /> Identify Log of test FNet length,&type of <br /> each line procedures,Ambient Psi or kpa Reading <br /> (Military) _ Change line,Flex <br /> as tested Temp,Weather,Etc Before After Before After connectors,Repairs <br /> DSL 1 1118 Start Line Test 50 .0660 2" FG 30' <br /> DSL 1 1128 Continue Line Test 49 F.0660 .0660F .0000 <br /> DSL 1 1138 Continue Line Test 50 50 F.0660 <br /> DSL 1 1148 Continue Line Test 50 50 .0660 .0660 <br /> ( DSL 1 1158 Continue Li Test tt 50 50 .0660- .066-1 .0000 ---- —� <br /> DSL 1 1208 Continue Line Test 50 50 .0660 x.0660 r .0000 Line Test Passed <br /> IF <br /> DSL 2 1219 Start Line Test 50 .0800 <br /> DSL 2 1229 cContinue Line Test 50 50 F.08001 .0800 F .0000 <br /> - - - - <br /> DSL 2 1239 1 Continue Line Test 56 50 .0800 .0800 .0000- <br /> DSL 2 1249 Continue Line Test 50 50 .0800 .0800 000 <br /> DSL 2 1259 Continue Line Test 50 50 .0800 .0800 .0000 ('''�L''innee Test Passed <br />