Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 7. LINE LEAK DETECTOR TESTING <br /> Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) <br /> Simulated release rate verified: (Check all that apply.) Yes No NA <br /> ® 3 GPH ® 0.1 GPH Ej 0.2 GPH <br /> Has the testing apparatus been properly calibrated? El <br /> For emergency generator tank systems, does the LLD create an audible and visual In <br /> alarm when a leak is detected? <br /> For mechanical LLDs, does the LLD restrict the flow through the pipe when a El 0 11 <br /> release is detected? <br /> For electronic LLDs, does the turbine automatically shut off when a release is <br /> detected? <br /> For electronic LLDs, does the turbine automatically shut off if any portion of the <br /> monitoring system is disabled or disconnected? <br /> For electronic LLDs, does the turbine automatically shut off if any portion of the <br /> monitoring system malfunctions or fails a tightness test? <br /> For electronic LLDs, have all accessible wiring connections been visually inspected <br /> for kinks and breaks? <br /> Were all items on the equipment manufacturer's maintenance checklist completed? <br /> Were all LLDs confirmed operational within regulatory requirements? ® ® El <br /> LLD 1D LLD Model Lines Monitored Pass Fail <br /> 91 99 LD 2000 91 Product Line El El <br /> 11 El <br /> 010 <br /> El in <br /> ® 0 <br /> ® rn <br /> ® El <br /> Describe all answers marked "No"or "Fail' and proposed remedy in Section 9. <br /> List all monitoring equipment either replaced or repaired in Section 9 <br /> Page 4 of 6 <br />