Laserfiche WebLink
1115000 Field Test Apparatus Page 1 of 1 <br /> Tanknalagy Line Leak Detector Test <br /> Work Order: 2364928 Date: 1/3/2024 <br /> Site Name/ID: 7-ELEVEN#43175/4873/43175/4873 <br /> Address: 35 NORTH CHEROKEE LANE <br /> City: LODI State: CA Zip: 95240 <br /> Tank ID 1 2 3 <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 5 5 4 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Red Jacket FX1V Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. UNKNOWN UNKNOWN UNKNOWN <br /> Pump Operating Pressure(psi) 30.00 43.00 49.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 30.00 43.00 49.00 <br /> *N/A for Electronic LD's <br /> Resiliency(ml) 65.00 110.00 100.00 <br /> *N/A for Electronic LD's <br /> Metering PSI 11 24 26 <br /> *N/A for Electronic LD's <br /> Opening Time(sec) 3 3 4 <br /> *N/A for Electronic LD's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: Al <br /> 41" Expire Date: 11/7/2024 <br /> Environmental Compliance for Petroleum Systems <br /> @2024 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />