Laserfiche WebLink
Closed <br /> ra. <br /> Figure 29 <br /> INSP 6. If there is no apparent damage or restrictions <br /> reinstall the valve per the above instructions and test <br /> per local requirements. <br /> 71 SO Performance Specifications <br /> This Overfill Prevention Valve has been manufactured <br /> and tested to,and met,the following California specifi- <br /> cations. Performance Requirement: Leak rate to be less <br /> than or equal to 0.17 CFH@2.0"W.C. <br /> Torque Specification <br /> Taptite Screws,#10-24 thread cutting,20 in-lbs mini- <br /> mum to 35 in-lbs maximum. Testable Models Only: <br /> Socket Adaptor, 1/4"NPT,3.5 ft-lbs (42 in-lbs) minimum <br /> to 5.0 ft-lbs (60 in-lbs) maximum. <br /> IMPORTANT: Leave these installation instructions <br /> and maintenance procedures with the station opera- <br /> tor. <br /> 19 <br />