Laserfiche WebLink
SAN J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> DINO MART 1 1001 E YOSEMITE AVE, MANTECA January 29, 2024 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 208 CCR 2716(a-e) Failure to comply with the designated operator inspection requirements. <br /> #1 OBSERVATION:The designated operator failed to check and note the correct test dates for the secondary <br /> containment test and the monitoring system certification on the designated operator inspection reports. <br /> The secondary containment date was cited on 1/17/2023 on the designated operator inspection reports dated <br /> 3/11/2023,4/10/2023, and 7/6/2023.The correct date for the secondary containment test is 1/13/2021. <br /> The monitoring system certification date was missing from the designated operator inspection report for 6/8/2023. <br /> The correct date for the monitoring system certification test is 1/13/2023. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall check that all required testing and <br /> maintenance for the UST system have been completed and document the dates they were done. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br /> the required information on the reports. <br /> #2 OBSERVATION: Designated operator reports were not signed within the required time frame. <br /> -The 1/13/2023, 2/10/2023, 3/11/2023, and 7/6/2023 designated operator report did not include the printed name of <br /> the owner/operator.. <br /> REGULATORY GUIDANCE:Within 48 hours of the completion of the designated UST operator visual inspection, <br /> the designated operator shall sign and provide the owner or operator with a copy of the inspection report. Within 72 <br /> hours of being provided a signed copy of the report,the owner or operator shall provide a description of each <br /> corrective action taken or to be taken and shall sign and date the report, acknowledging the identified compliance <br /> issues. <br /> CORRECTIVE ACTION: Ensure all designated operator inspection reports are completed and signed within the <br /> required time frame in the future. <br /> This is a repeat violation, Class II. <br /> 215 CCR 2715 Designated operator, service tech, or installer did not possess current certifications. <br /> OBSERVATION: Felix Ramirez performed the 4/10/2023 inspections and did not have a current ICC certification at <br /> the time of the inspections. <br /> REGULATION GUIDANCE:A designated operator shall have a current ICC certification at the time of the <br /> inspections. <br /> CORRECTIVE ACTION: Ensure that any designated operator who performs inspections at this facility has current <br /> ICC certification, and submit documentation to the EHD showing that Felix Ramirez had current ICC certification <br /> when the 4/10/2023 inspections were performed. <br /> This is a Class II violation. <br /> FA0000421 PR0231876 SCO01 01/29/2024 <br /> EHD 23-01 Rev.12/06/2021 Page 6 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />