_ anknology LDT 5000 Field Test Apparatus Page 1 of 1 <br /> TLine Leak Detector Test <br /> Work Order: 2364792 Date: 3/14/2024 <br /> Site Name/ID. 7-ELEVEN#32262, MKT 2368(N-3940-1 /32262 <br /> Address: 2360 W GRANTLINE 1-205 OFF RAMP <br /> City: TRACY State: CA Zip: 95376 <br /> Tank ID T4 RUL T5 MUL T6 PUL <br /> Product REG UNLEAD MIDGRADE PREMIUM <br /> Product Line 1 1 1 <br /> Tested From 1 1 1 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. unreadable 12121067 12011032 <br /> Pump Operating Pressure(psi) 30.00 33.00 32.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 30.00 33.00 32.00 <br /> NIA for Electronic Lo's <br /> Resiliency(ml) 180.00 240.00 200.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 17 21 19 <br /> NIA for Electronic Lo's <br /> Opening Time(sec) 6 4 2 <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus S//aldivar Certification#: 115237 <br /> Technician Signature: /-1 14/- Expire Date: 11/7/2024 <br /> Environmental Compliance for Petroleum Systems <br /> ©2024 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />