Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for NATIONAL PETROLEUM MANTECA as of March 15, 2024. <br /> Open violations from September 05, 2023 inspection <br /> Violation#208-Failure to comply with the designated operator inspection requirements. <br /> OBSERVATION: The designated operator failed to check and note all required items on the visual inspection <br /> reports.The incorrect and missing information included the following from the inspection reports: <br /> -The DO reports did not include the name of the UST owner/operator. <br /> REGULATION GUIDANCE: During the visual inspection,the designated operator shall check that all required <br /> testing and maintenance for the UST system have been completed and shall check all required items on the report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing visual inspections at this facility are including <br /> all of the required information on the reports. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Violation#214-Failure to comply with UST operating permit conditions. <br /> OBSERVATION: The facility is not in compliance with the written conditions of the operating permit. The racing fuel <br /> 100 and 110 tanks leak detector annual testing has not been conducted. <br /> REGULATION GUIDANCE: The owner and operator of underground storage tank(UST)systems shall comply with <br /> all requirements of the permit issued for the operation of the UST system. <br /> CORRECTIVE ACTION: Immediately take all necessary actions to bring these UST systems into compliance to <br /> avoid the tanks being red tagged. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Violation#301 -Failure to operate UST system to prevent unauthorized releases including leaks,spills and <br /> overfills. <br /> OBSERVATION: Dark staining were observed on concrete surrounding UDC#9. <br /> REGULATION GUIDANCE: The underground storage tank system shall be operated to prevent unauthorized <br /> releases, including spills and overfills. <br /> CORRECTIVE ACTION: Immediately complete clean up. <br /> Page 3 of 4 <br />