Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-87-PS 2-89-PS 3-91-PS 4-Diesel-PS <br /> Sump Manufacturer Western FG Western FG Western FG Western FG <br /> Sump Depth (inches) 40" 40" 40" 40" <br /> Sump Bottom to Top of 11" 11" 10" 18" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:52 10:10 10:00 9:50 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 11:22 10:40 10:30 10:20 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Lss/FailCriteria > .002 > .002 > .002 > .002 <br /> htness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID UDC 1&2 UDC 3&4 UDC 5&6 UDC 7&8 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 9" 9" 9" 9" <br /> Sump Bottom to Top of BP BP BP BP <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:07 11:20 11:18 11:25 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 11:37 11:50 11:48 11:55 <br /> Final Reading > .030 .001 .001 > .030 <br /> Change in Reading > .030 0 0 > .030 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ❑ Pass ® Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ® Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />