Laserfiche WebLink
_ anknology LDT 5000 Field Test Apparatus Page 1 of 1 <br /> TLine Leak Detector Test <br /> Work Order: 2364985 Date: 6/27/2024 <br /> Site Name/ID. TESORO/SPEEDWAY#68154/46641/4681 <br /> Address: 2500 W LODI <br /> City: LODI State: CA Zip: 95242 <br /> Tank ID 1 2 3 4 <br /> Product REGULAR MIDGRADE PREMIUM Diesel <br /> Product Line 1 1 1 1 <br /> Tested From 2 2 2 2 <br /> Existing/New Existing Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 Veeder Root FX1 D <br /> Serial No. UNKNOWN UNKNOWN UNKNOWN UNKNOWN <br /> Pump Operating Pressure(psi) 30.00 29.00 37.00 27.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 3.00 <br /> Holding PSI 30.00 29.00 37.00 27.00 <br /> NIA for Electronic Lo's <br /> Resiliency(ml) 180.00 155.00 205.00 125.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 20 15 17 10 <br /> NIA for Electronic Lo's <br /> Opening Time(sec) 2 9 3 3 <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus S//aldivar Certification#: 115237 <br /> Technician Signature: /-1 14/- Expire Date: 11/7/2024 <br /> Environmental Compliance for Petroleum Systems <br /> ©2024 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />