Laserfiche WebLink
Page 1 of 2 <br />nahLEAK DETECTION <br />1` E C H N O L O G I E S INC <br />Providers for MDleak° MSleak° DPleak°, MCleak°and <br />PHDleako Testing Technologies <br />2765 East Wieding Road ❑ Tucson, AZ 85706 ❑ Phone 855-255-5325 ❑ FAX: 1-520-509-3720 <br />Facility Certification CONFIDENTIAL <br />Test Type: California ELD New Constr Test (No/Fuel) Job #: 5644 <br />Facility Name: Gas Station PO #: <br />Prepared For: Central Cal Services Inc <br />Site Address: 630 E 11th St <br />City: Tracy <br />State and Zip: CA 95304 <br />Start Date: 11/14/2024 End Date: 11/15/2024 <br />SYSTEM <br />Test MDL <br />TK -1 87 <br />TK -2 91 <br />TK -3 DSL VR <br />Product Primary MDlcak: <br />0.005 GPH <br />PASS <br />PASS <br />PASS <br />Product Secondary: <br />0.1 GPH <br />PASS <br />PASS <br />PASS <br />Vent Prima MDlcak: <br />0.005 GPH <br />PASS <br />PASS <br />PASS <br />VR Primary MDlcak: <br />0.005 GPH <br />PASS <br />PASS <br />NA <br />VR Secondary: <br />0.1 GPH <br />PASS <br />PASS <br />NA <br />MDleak Tank: <br />0.005 GPH <br />PASS <br />PASS <br />PASS <br />Turbine Sump Fittings: <br />0.005 GPH <br />PASS <br />PASS <br />PASS <br />Fill/Vapor Sump Fittings: <br />0.005 GPH <br />PASS <br />PASS <br />PASS <br />UDC Fittings: <br />0.005 GPH <br />PASS <br />PASS <br />PASS <br />Fill Bucket: <br />0.005 GPH <br />PASS <br />PASS <br />PASS <br />Vapor Bucket: <br />0.005 GPH <br />PASS <br />PASS <br />NA <br />Vent Box Fittings <br />0.005 GPH <br />PASS <br />PASS <br />PASS <br />Fill Spill Bucket Hydro: <br />0.1 GPH <br />PASS <br />PASS <br />PASS <br />Vapor Bucket Hydro: <br />0.1 GPH <br />PASS <br />PASS <br />NA <br />