Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ❑x Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ❑x Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-PS-87 2-PS-91 3-PS-Dsl. <br /> Sump Manufacturer Western FG Western FG Western FG <br /> Sump Depth (inches) 40 1/2" 41" 40" <br /> Sump Bottom to Top of 20 1/2" 17" 13" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:33 8:47 8:42 <br /> Initial Reading .001 .001 .001 <br /> Test End Time 10:03 9:17 9:12 <br /> Final Reading .001 .001 .001 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 <br /> Tightness Test Results © Pass ❑ Fail © Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 1&2 UDC 3&4 UDC 5&6 UDC 7&8 <br /> Sump Manufacturer Bendell Corp Bendell Corp Bendell Corp Bendell Corp <br /> Sump Depth (inches) 15" 15" 15" 15" <br /> Sump Bottom to Top of BP BP BP BP <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 8:52 8:57 9:02 9:07 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 9:22 9:27 9:32 9:37 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ❑x Pass ❑ Fail ❑x Pass ❑ Fail © Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3of5 <br />