My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2024
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
B
>
BESSEMER
>
1019
>
2800 - Aboveground Petroleum Storage Program
>
PR0515715
>
COMPLIANCE INFO_2024
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
9/6/2024 2:45:36 PM
Creation date
7/30/2024 12:46:20 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2800 - Aboveground Petroleum Storage Program
File Section
COMPLIANCE INFO
FileName_PostFix
2024
RECORD_ID
PR0515715
PE
2832
FACILITY_ID
FA0010328
FACILITY_NAME
MOUNTAIN VALLEY EXPRESS INC
STREET_NUMBER
1019
STREET_NAME
BESSEMER
STREET_TYPE
AVE
City
MANTECA
Zip
95337
APN
22104067
CURRENT_STATUS
01
SITE_LOCATION
1019 BESSEMER AVE
P_LOCATION
04
P_DISTRICT
005
QC Status
Approved
Scanner
SJGOV\kblackwell
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
13
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - AST Non-Qualified Inspection Report <br /> Facility Name: Facility Address: Date: <br /> MOUNTAIN VALLEY EXPRESS INC 1019 BESSEMER AVE, MANTECA June 20 2024 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> person in accordance with industry standards. Submit proof of correction/test results to the EHD. <br /> This is a repeat violation (Class 2) Violation. <br /> 61 Code of Fed Regulations 112.8(c)(8)(v)4030022-Liquid level sensing devices regularly tested to ensure proper <br /> operation. <br /> OBSERVATION: Liquid level sensing devices for the 10,000 gallon diesel#2 tank, 550 gallon used oil tank, and 600 <br /> gallon new oil tank have not been tested. <br /> -4.2.8:ASTs equipped with liquid level sensing devices are tested on a monthly basis during the monthly inspection of <br /> the facility. Monthly inspection records end on 9/16/2022. <br /> REGULATION GUIDANCE: (c)(8)(v)You must regularly test liquid level sensing devices to ensure proper operation. <br /> CORRECTIVE ACTION: Liquid level sensing devices must be installed in accordance with CFR 112.8 and shall be <br /> regularly tested to ensure proper operation. Immediately conduct all necessary testing of all liquid level sensing <br /> devices to ensure proper operation, submit test results to the EHD. <br /> This is (Class 2)Violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been OR will be taken for each violation, and any supporting <br /> paperwork, by 7/21/2024. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead of <br /> having them sign. Starting September 1, 2018, all in-office CERS help will be provided at the EHD hourly rate <br /> ($162). To schedule an appointment, please call (209)468-3420. <br /> The following was observed during this inspection: <br /> -10,000 gallon diesel #2 tank <br /> -550 gallon used oil -waste tank <br /> -New oil tank previously reported as 600 gallon single-walled, unknown capacity <br /> -55 gallon portable drum of transmission fluid <br /> The following was provided during with this report: Schedule of free CUPA classes, return to compliance and <br /> corrective action statement, and inspection photos <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING THIS <br /> FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: June 20, 2024 Inspector: Inspector Phone: <br /> Printed Name and Title: Matthew Won, EHS (209)616-3029 <br /> Dan Souza, Environmental <br /> Contact <br /> FA0010328 PR0515715 SCO01 06/20/2024 <br /> EHD Rev.12/06/2021 Page 7 of 7 CP22-AST Non-Qualified OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />
The URL can be used to link to this page
Your browser does not support the video tag.