Laserfiche WebLink
ENVIRONMENTAL AGRICULTURAL <br /> Analytical Chemists <br /> December 22, 2025 <br /> Lab No. : STK2558606-001 <br /> San Joaquin Co. Environmental Health Dep Customer No.: 3017919 <br /> Description :Wellhead Matrix : Drinking Water <br /> Project :18660 E. Tobacco Road, Linden- Sampled On : December 8, 2025 at 08:17 <br /> WP0043911 <br /> Drinking Water Interpretations <br /> Summary: Your water was acceptable for all items tested on this sample report. Details are presented below: <br /> Constituent Result Units MCL Result Compared to MCL <br /> Inorganic -Primary Less Than or Equal Exceeded <br /> Fluoride 0.1 mg/L 2 PASS <br /> Nitrate + Nitrite as N 0.6 mg/L 10 PASS <br /> Nitrate as NO3 2.6 mg/L 45 PASS <br /> Nitrate Nitrogen 0.6 mg/L 10 PASS <br /> Nitrite as N ND mg/L 1 PASS <br /> Zinc ND ug/L 5000 PASS <br /> Inorganic -Secondary Less Than or Equal Exceeded <br /> Chloride 5 mg/L 500 PASS <br /> Copper ND ug/L 1000 PASS <br /> Iron 30 ug/L 300 PASS <br /> Manganese ND ug/L 50 PASS <br /> Specific Conductance 244 umhos/cm 1600 PASS <br /> Sulfate 13.1 mg/L 500 PASS <br /> Total Dissolved Solids 190 mg/L 1000 PASS <br /> Other Less Than or Equal Exceeded <br /> Copper ND ug/L 1300** PASS <br /> Drinking Water Interpretations without MCL <br /> Constituent Result Units Range Interpretation <br /> Aggressiveness Index 12.0 -- 10 to 12 IModerately Aggressive. <br /> Langelier Index(20°C) 0.1 --- >0 Water is supersaturated with respect to calcium carbonate <br /> (CaCO3)and scale forming may occur. <br /> Drinking Water Interpretations without MCL <br /> Constituent Result Units Range Interpretation <br /> Aggressiveness Index 12.0 10 to 12 IModerately Aggressive. <br /> Langelier Index(20°C) 0.1 -- >0 <br /> Water is supersaturated with respect to calcium carbonate <br /> (CaCO3)and scale forming may occur. <br /> ND=Non-Detect <br /> Definitions <br /> MCL The maximum level at which a constituent may be present and be considered acceptable for potability or aesthetics. <br /> Primary Items listed as primary are regulated because of health concerns. If there is a failure for a primary constituent <br /> treatment is normally required. <br /> Section:Drinking Water Interpretations Page 4 of 8 Page 4 of 8 <br /> Corporate Offices&Laboratory Office&Laboratory Office&Laboratory Office&Laboratory Office&Laboratory <br /> 853 Corporation Street 2500 Stagecoach Road 563 E.Lindo Avenue 3442 Empresa Drive,Suite D 9411 W.Goshen Avenue <br /> Santa Paula,CA 93060 Stockton,CA 95215 Chico,CA 95926 San Luis Obispo,CA 93401 Visalia,CA 93291 <br /> TEL:(805)392-2000 TEL:(209)942-0182 TEL:(530)343-5818 TEL:(805)783-2940 TEL:(559)734-9473 <br /> CA ELAP Certification No.1573 CA ELAP Certification No.1563 CA ELAP Certification No.2670 CA ELAP Certification No.2775 CA ELAP Certification No.2810 <br />