Laserfiche WebLink
PANEL P 125 AMP FRAME MAIN LUG ONLY <br /> FUELING SYSTEM 120/24OV, 1 PHASE, 3 WIRE BRANCH CB'S± BOLT-ON, SIZE AS INDICATED <br /> TRACY TRIANGLE 30 CIRCUIT,SURFACE MTD.NEMA I INTERRUPTING RATING: 42,000 AIC Z <br /> Lmn <br /> DESIGNATION CKT.BPoCR VOLT-AMPS CKT.BFXR DESIGNATION � V' <br /> CKT. PANEL WIRE SERVES SERVES WIRE PANEL CKT. z <br /> NO. SPACE AMP POLE AW3 LOAD A B LOAD AM AMP POLE SPACE NO. �y N U <br /> li I <br /> 1 1 20 2 4*12 DISPENSER 1/2 500 1900 1400 SUBMERGED TURBINE PUMP (STP) 010 30 2 2 2 LML w a) <br /> w � O �r <br /> 3 3 (SWITCHED NEUTRAL) 0 1400 1400 2 hp REG (0-1) 4 4 LML Z � I (jl <br /> 5 5 20 2 #12 DISPENSER 3/4 500 1900 1400 SUBMERGED TURBINE PUMP (STP) 010 30 2 6 6 Z O cv <br /> - - - - - - N 0'12'w=50- - - - - - - _1 (SWITCHED NEUTRAL) 0 1400 1400 2 hp SUPER (131) 8 8 0 m~ <br /> g g 20 2 #12 DISPENSER 5/6 500 1-100 1200 SUBMERGED TURBINE PUMP (STP) 010 30 2 10 10 J <br /> 11 11 (SWITCHED NEUTRAL) 0 1200 1200 1.5 hp DIESEL 12 12 <br /> 13 13 20 2 #12 DISPENSER -1/0 500 1_100 1200 SUBMERGED TURBINE PUMP (STP) 012 20 1 14 14 <br /> 15 15 (SWITCHED NEUTRAL) 0 1200 1200 1.5 hp E55 16 16 <br /> / I 11 1-1 20 2 #12 SPARE 0 0 0 SPACE IS 18 111 <br /> 19 19 ARE 0 500 500 ESO 012 20 1 20 20 CL <br /> 21 21 20 2 012 SPARE 0 0 0 SPACE 22 22 <br /> 23 23 SPARE 0 1500 1500 INTERCOM #12 20 1 24 24 <br /> CL 25 25 20 1 #12 MONITOR 1,000 1500 500 OVERFILL ALARM 012 20 1 26 26 CL <br /> 2-1 2-7 SPARE 0 0 0 SPACE 28 28 <br /> CL 2'3 2c3 20 1 #12 ELLDs 500 500 0 SPACE 30 30 <br /> NEW T <br /> QSR 6A48=SF. C-STORE � v, <br /> TOTAL CONNECTED LOAD 9,200 -1,200 <br /> I 1 2 I w0Uy <br /> BUS A: g,200 vA CONTINUOUS LARGEST CONNECTED TOTAL N.E.G. W q O U l N <br /> BUS B: -1,200 VA LOAD: (CL) MOTOR LOAD: (LML) LOAD: COMPUTED LOAD: W Lu U > I U <br /> TOTAL: 16,400 VA C 2,500 VA x 0.25) + ( 2,800 VA x 0.25) + 16,400 VA = 16,400 VA J O m <br /> AMPERES 120/240V, I PHASE = 14 AMPS <br /> O f- cYl U <br /> Z � <br /> 4) I � _ � � " � <br /> ----------------------- --------------------------- I pQ�1CL MOVIES � c i W <br /> P-20 I- PROVIDE PLASTIC PHENOLIC NAMEPLATE AND TYPED PANEL CIRCUIT DIRECTORY. I - <br /> 2. PROVIDE ISOLATED GROUND BUSS FOR ISOLATED GROUND CIRCUIT BREAKER. <br /> 3. PROVIDE SEAL-OFF FITTINGS FOR ALL CIRCUITS ENTERING PANEL FROM CLASS I, DIV. 2 AREAS. Q <br /> ® a ® IJI n <br /> (E)FREEWAY SIGN <br /> FUEL SYSTEM ELECTRICAL KEYNOTES 0 LLI <br /> I. INSTALL NEW FUEL SYSTEM CONTROLS. SUPPLY AND INSTALL NEW FUEL SYSTEM RELATED PANELS, WIREWAYS, CONDUIT, CONDUCTORS, 5EALOFF5, ETC., A5 Z <br /> ------------------------------ a?------------------------------ lll <br /> w w REQUIRED, PER MNFR. RECOMMENDATIONS. REFER TO AND COORDINATE W/ THE REQUIREMENTS OF THE ARCHITECTURAL AND ELECTRICAL SHEETS. IF U <br /> CONFLICTS OCCUR BETWEEN THESE AND OTHER DRAWINGS NOTIFY THE ARCHITECT / ENGINEER. <br /> z CNI CANOPY I m <br /> ---------- - - -------- -------------------------------------- - <br /> 2. NEW (N) MONITORING PANEL. INSTALL NEW MONITORING COMPONENTS PER MNFR. RECOMMENDATIONS. <br /> a P-20 9 12 Q P-20 <br /> 3 I I <br /> o o �,-p 4 0 0 o 0 4 �o o ✓ 3. (N) EMERGENCY SHUTOFF (E.S.O.) W/ 3/4" C.. SEE ALSO FUEL SYSTEM SITE PLAN. INSTALL SIGNS(&) PER CFC 2303.2. MUSHROOM PUSH-BUTTON W/ <br /> R <br /> \� <br /> E. ; W g PLEXIGLAS COVER (O NEMA 3R ENCL.). CONNECT TO MAIN SHUNT TRIP CIRCUIT, WIRE PER MNFR. REQUIREMENTS. ((3) #12ga. - MIN., SEE KEYNOTES 12, 15) <br /> o I O � _ <br /> 4. (N) 3/4" G. FOR STP (SUBMERGED TURBINE PUMP) W/ #10'S AND #10 GND., (MIN.) VIA WIREWAY. (POWER (4) #lOga., ) N m <br /> 00 oo O 00 00 w o <br /> NEW FUELING ( 5. (N) 1" C. HOMERUN TO WIREWAY FOR ELECTRONIC LINE LEAK DETECTOR, SUMP FLOAT SWITCH, VACUUM/HYDRO SENSORS, SUMP MINI-HYDRO SENSOR AND w <br /> ---------------- 13 1� 15 16 -----------------JI TANK GAUGE PROBE. ((0) 2#18ga. SHD. CABLE) N II <br /> 6. (N) 3/4" C. HOMERUN TO WIREWAY W/ 3/4" LOOPED (NO LOOP AT DIESEL) FOR HYDROSTATIC SENSOR, SUMP FLOAT SWITCH AND SUMP MINI-HYDRO on N OL <br /> ------------------------------ 0 --- --- ---------------------- PAYP I SENSORS. (INTERSTITIAL (1) 2#18ga. SHD, CABLE, FILL (2) 2#18ga. SHD, CABLE) Z <br /> 05 P-2 O O O U378 O O � O O I �. (N) 3/4" G. HOMERUN TO WIREWAY FOR DISPENSER N.V., TYP.. WIRE PER MNFR. REQUIREMENTS. C3+O's C5) #12ga., (2) #14ga. TWISTED - FOR 3+1's ADD (1) #12 ga.) � � � � w O <br /> S. (N) 3/4" C. HOMERUN TO WIREWAY FOR MONITORING L.V., TYP.. WIRE PER MNFR. REQUIREMENTS. (MONITOR (3) 2#18ga. SHD. CABLE) Q U 0 -� >� LL <br /> �2Qa 87 a��ffig <br /> - <br /> ° 9 3/4" C. LU& GAT 5/ETHERNET FOR EMV READY CARD SYSTE TYP WIRE PER MNFR <br /> (N) . HOMERUN TO WIREWAY FOR DISPENSER INTERCOM P - - M, .. <br /> REQUIREMENTS. (INTERCOM MIN. (2) #14ga. TWISTED, (2) #16ga.) <br /> --_ J --- -----, - 10 _ 10. (N) NEW 3/4" G. FROM VENT CONTAINMENT / MONITORING TO WIREWAY, W/ SEAL-OFFS AS REQUIRED. (SUMP - (2) 2#18ga. SHD. CABLE, <br /> 0 11 P-20 CCVP - (1) 2#18ga. SHD. CABLE) <br /> O II. (N) NEW 3/4" C. TO WIREWAY FOR OVERFILL ALARM. WIRE PER MNFR. REQUIREMENTS. ((4) #12ga.) �t � <br /> - - - - - uj o0 <br /> CURB.GUTTER <br /> "m W AL - - - - - - 12. HOMERUN CIRCUIT, TYPICAL. MINIMUM (2) #12'S AND (1) #12 GND. IN 3/4" C. W/ MAXIMUM (3) HOMERUN CIRCUITS PER CONDUIT. NUMBER OF ARROWHEADS � J V -4 _ � O <br /> ER<SIDEWALK INDICATES NO. OF HOMERUN CIRCUITS. BRANCH CIRCUITS GREATER THAN 15 FT. TO FIRST LIGHT FIXTURE OR OUTLET SHALL 5E MINIMUM #10 AWG. V Z O 65 U <br /> INCREASE WIRE AND CONDUIT SIZE PER MNFR. AND/OR CODE REQUIREMENTS. V Z J ly z <br /> 13. ALL CONDUITS AT TRAFFIC AREAS TO 5E BURIED A MIN. OF 24" (12" AT NON-TRAFFIC, AREAS). Q W <br /> NORTH T R A C Y B O U L E V A R D 14. LOCATE SEAL-OFF FITTINGS PER GEC 514 AND HAZARDOUS LOCATION SPECIFICATIONS, THIS SHEET, FOR CIRCUITS TO DISPENSING AREA AND LL <br /> _ U O <br /> UNDERGROUND FUEL TANKS, AS APPLICABLE. <br /> � z1­4 <br /> F U E L SYSTEM E L E C T R I C A L S I T E P L A N Z 15. INSTALL (CONSULT OWNER PROVIDED EQUIPMENT LIST) AND/OR PROVIDE AND INSTALL ADDITIONAL SYSTEM COMPONENTS, INCLUDING BUT NOT LIMITED � <br /> �Hol SCALE:P = I0' CUSEGRAPHICSCALEFORREDUCEDPLOTSI TO CONDUITS, HIGH 4 LOW VOLTAGE CONDUCTORS FOR POWER, MONITORING AND COMMUNICATIONS (INTERCOM 4 CONTROL), J-BOXES, 5EALOFF5, ETC. A5 <br /> SITE PLAN DEVELOPED PRIMARILY FROM RECORD DRAWINGS 0 10 20 40 AND PHOTO REVIEW. THIS IS NOT A SURVEY. REQUIRED TO PROVIDE A COMPLETE, WORKABLE SYSTEM PER MNFR. AND CODE REQUIREMENTS. INSURE THAT CONDUCTORS MATCH MNFR'&. REQ'5. FOR <br /> PURPOSE AND CONDUIT LENGTHS. <br /> 16. CONDUIT RUNS ARE INTENDED AS SCHEMATIC, AND MAY 5E EXAGGERATED FOR DRAFTING CLARITY. FIELD CONDITIONS AND STANDARD PRACTICES <br /> MAY INDICATE DIFFERENCES AND ARE EXPECTED. <br /> (CFG 2303.2.1) HEIGHT. THE HEIGHT OF THE EMERGENCY DISCONNECT SWITCH SHALL 5E NOT LESS THAN 42 INCHES (106-1 mm) ;2 HAZARDOUS LOCATION SPECIFICATIONS <br /> AND NOT MORE THAN 48 INCHES (1219 mm) MEASURED VERICALLY, FROM THE FLOOR LEVEL TO THE ACTIVATING BUTTON. <br /> U U U U <br /> A. FUEL SYSTEM CONTRACTORS AND INSTALLERS ARE EXPECTED AND REQUIRED TO HAVE CURRENTLY REQUIRED EQUIPMENT MANUFACTURERS' Z Z Z Z <br /> CERTIFICATIONS AND APPROVALS FOR INSTALLATION OF ALL OF THE FUEL SYSTEM RELATED EQUIPMENT AND WORK, INCLUDING ELECTRICAL -4 4 4 -4 <br /> COMPONENTS, AND TO PROVIDE A COMPLETE, WORKABLE SYSTEM PER MNFR. AND CODE REQUIREMENTS. > IL Ih � <br /> 5. PROVIDE EXPLOSION PROOF JUNCTION BOX AND SEAL-OFF FITTINGS PER ARTICLE 514 OF THE GEC FOR HAZARDOUS LOCATIONS. � <br /> C. ALL CONDUIT AND WIRING TO FUEL DISPENSERS AND SUBMERSIBLE PUMPS SHALL 5E INSTALLED AND USED IN ACCORDANCE WITH FLAMMABLE AND <br /> COMBUSTIBLE LIQUIDS CODE NFPA 30 AND APPLICABLE PROVISIONS OF THE LATEST EDITION OF THE CALIFORNIA ELECTRIC CODE ARTICLE 514, MOTOR W N N (V <br /> FUEL DISPENSING FACILITIES, INCLUDING THE FOLLOWING: PROVIDE EXPLOSION PROOF/SEAL-OFF FITTINGS ON ALL POWER SUPPLY LINES LOCATED AT �f m <br /> FUEL DISPENSERS, SUBMERSIBLE PUMPS AND ANY OTHER ELECTRICAL EQUIPMENT LOCATED IN A 20' RADIUS OF THE GASOLINE FUEL DISPENSER ISLAND. <br /> AN AREA PER FIGURE 514.3 OF THE GEC IS DEFINED AS A HAZARDOUS LOCATION WITHIN A 20' RADIUS FROM THE END OF EACH DISPENSER. ALL LQ @ @ @ @ <br /> ELECTRICAL EQUIPMENT AND WIRING WITHIN THIS AREA SHALL 5E PER CEC 514. <br /> D. GEC 541.9 SEALING (OF DISPENSERS) - A LISTED SEAL (EXPLOSION PROOF SEAL-OFF FITTING) SHALL 5E PROVIDED IN EACH CONDUIT RUN ENTERING OR <br /> LEAVING A DISPENSER OR ANY CAVITIES OR ENCLOSURES IN DIRECT COMMUNICATIONS THEREWITH. THE SEALING FITTING OR LISTED EXPLOSIONPROOF � o W <br /> REDUCER AT THE SEAL SHALL 5E THE FIRST FITTING AFTER THE CONDUIT EMERGES FROM THE EARTH OR CONCRETE. (5) AT BOUNDARY- ADDITIONAL SEALS > .4 z w% <br /> SHALL 5E PROVIDED IN ACCORDANCE WITH 501.15. SECTIONS 501.15(A)(4) AND (5)(2) SHALL APPLY TO HORIZONTAL A5 WELL A5 TO VERTICAL BOUNDARIES ., w m <br /> LL <br /> OF THE DEFINED GLASS I LOCATIONS. Z W �� Q-ILL w 0 <br /> ���w ,t <br /> E. PROVIDE EXPLOSION PROOF/SEAL-OFF FITTINGS AT THE POINT OF CONDUIT STU5UP ENTRANCE (AT PANEL50ARD) INTO THE SERVICE BUILDING FOR ALL Q �,, "D 'y � Is I) <br /> POWER SUPPLY CONDUITS TO FUEL DISPENSERS, SUBMERSIBLE PUMPS AND OTHER ELECTRICAL EQUIPMENT LOCATED IN THE A50VE DEFINED J (n w o w Lt-o A o a <br /> HAZARDOUS LOCATIONS. N a W If>- m Q>- A M O <br /> (f)�O�y: p � <br /> F. ALL BELOW GRADE CONDUIT RUNNING THROUGH (ENTERING OR LEAVING - THEN THE ENTIRE CONDUIT RUN SHALL 5E RGS) THE GLASS 1 DIVISION 1 N (L a Q ®0 HAZARDOUS LOCATION AS DESCRIBED ABOVE AND AS DEFINED PER CEC ARTICLE 514 SHALL 5E RGS. RIGID NON-METALLIC CONDUIT (PVG) MAY ONLY LLI W 0 -1 <br /> 5E USED AS LONG AS THE PROVISIONS OF NEC ARTICLE 514.0 EXCEPTION NO. 2 ARE STRICTLY ADHERED TO INCLUDING THE REQUIREMENTS FOR AN = J p <br /> EQUIPMENT GROUNDING CONDUCTOR IN THE RIGID NON-METALLIC CONDUIT AND THE EQUIPMENT GROUNDING CONDUCTOR MUST 5E BONDED TO THE cn w 7 o() o z fl- <br /> EXPLOS ION-PROOF RACEWAY SYSTEM INSIDE THE DISPENSER (THIS MAY 5E ACCOMPLISHED 5Y TERMINATING THE EQUIPMENT GROUNDING CONDUCTOR W J Z �w o z <br /> ON THE GROUND SCREW PROVIDED IN THE JUNCTION BOX). WHERE RIGID NON-METALLIC CONDUIT IS USED IT SHALL 5E BURIED A MINIMUM OF 2 FEET w a <br /> BELOW EARTH AND THREADED RIGID METAL CONDUIT SHALL 5E USED FOR THE LAST 2 FEET OF THE UNDERGROUND RUN TO EMERGENCE OR POINT OF LL W o w� w L o o <br /> CONNECTION TO THE ABOVE GROUND RACEWAY. 0 w <br /> G. EACH CIRCUIT LEADING TO OR THROUGH A DISPENSING PUMP SHALL 5E PROVIDED WITH A SWITCH TO DISCONNECT SIMULTANEOUSLY FROM THE SOURCE <br /> OF SUPPLY ALL CONDUCTORS OF THE CIRCUIT INCLUDING THE GROUNDED CONDUCTOR. <br /> A <br /> H. THE METAL PORTION OF DISPENSING PUMPS, METAL RACEWAYS AND ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRIC � <br /> EQUIPMENT, REGARDLESS OF VOLTAGE SHALL 5E GROUNDED AS PROVIDED IN GEC ARTICLE 250. (('�VVL <br /> I. CONDUCTORS SHALL 5E: THWN WIRE, GAS 4 OIL RESISTANT, AND 5ELDEN (OREQUAL) 88160 MULTI-CONDUCTOR, SINGLE PIIIIIIIIIIIIIIIIIIIIIPAIR CABLE (FOR 2#ISGA. SHD. GABLE). T = 6 <br /> REN S 31--86 ~ <br /> K4*op <br /> CAl-;0O OF 9 'PET' SHEETS <br />