Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ® Manufacturer © Industry Standard ® Professional Engineer <br /> Test Type El Pressure ® Vacuum ® Hydrostatic <br /> Test Equipment Used: INCON-TS1000-Hyd-15min <br /> Sump/UDC ID DSL 1 STP DSL 2 STP NORTH UDC SOUTH UDC <br /> Sump Manufacturer N/A N/A N/A N/A <br /> Sump Depth (inches) N/A N/A N/A N/A <br /> Sump Bottom to Top of N/A N/A N/A N/A <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 13:15 13:51 13:51 <br /> Initial Reading 4.1600 2.0284 1.2525 <br /> Test End Time 13:30 14:07 14:07 <br /> Final Reading 4.1600 2.0296 1.2532 <br /> Change in Reading 0 .0011 .0007 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results r Pass ® Fail 0 Pass ® Fail Fr Pass ® Fail ® Pass-® Fail <br /> Sump/UDC ID SLAVE UDC <br /> Sump Manufacturer N/A <br /> Sump Depth (inches) N/A <br /> Sump Bottom to Top of N/A <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 14:09 <br /> Initial Reading 3.8543 <br /> Test End Time 14:24 <br /> Final Reading 3.8545 <br /> Change in Reading .0002 <br /> ass ail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results 0 Pass Fr Fail Fr Pass Fail ® Pass © Fail r Pass r Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail' and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />