Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2384443 Date: 6/16/2025 <br /> Site Name/ID: TESORO/SPEEDWAY#68154/46641/4681 <br /> Address: 2500 W LODI <br /> City: LODI State: CA Zip: 95242 <br /> Tank ID 1 2 3 4 <br /> Product REGULAR MIDGRADE PREMIUM Diesel <br /> Product Line 1 1 1 1 <br /> Tested From 1 1 1 7 <br /> Existing/New Existing Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 Veeder Root FX1D <br /> Serial No. UNKNOWN UNKNOWN UNKNOWN UNKNOWN <br /> Pump Operating Pressure(psi) 40.00 26.00 36.00 26.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 3.00 <br /> Holding PSI 40.00 26.00 36.00 20.00 <br /> *N/A for Electronic LD's <br /> Resiliency(ml) 255.00 165.00 200.00 125.00 <br /> N/A for Electronic LD's <br /> Metering PSI 20 14 22 10 <br /> N/A for Electronic LD's <br /> Opening Time(sec) 4 5 5 3 <br /> N/A for Electronic LD's <br /> Test Results Pass Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Carlos Zaragoza Certification#: 209437 <br /> Technician Signature: Expire Date: 5/28/2027 <br /> Environmental Compliance for Petroleum Systems <br /> ©2025 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />