Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 8. IN-TANK GAUGING TESTING <br /> ❑ Check this box if tank gauging is used only for inventory control. <br /> ❑ Check this box if NO tank gauging equipment is installed. Yes No NA <br /> Do not complete this section if either box is checked. <br /> All wiring has been: 1) visually inspected for kinks, breaks and proper entry and ❑ ❑ 12 <br /> termination; and 2 tested for ground faults? <br /> Were all in-tank gauging probes visually inspected for damage and residue buildup ❑ ❑ 12 <br /> to ensure that floats move freely, functionally tested, and confirmed operational? <br /> Was accuracy of system's product level readings tested? ❑ ❑ 52 <br /> Was accuracy of system's water level readings tested? ❑ ❑ 12 <br /> Were all probes reinstalled properly? ❑ ❑ 12 <br /> Were all items on the equipment manufacturer's maintenance checklist completed? ❑ I ❑ Kj <br /> Probe ID Probe Model Tanks Monitored Pass Fail <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ I ❑ <br /> 9. COMMENTS <br /> Describe all answers marked "No"or "Fail'and proposed remedy. <br /> List all monitoring equipment either replaced or repaired. <br /> THIS MONITORING SYSTEM CERTIFICATION IS FOR THE L8, DIESEL TANK ANNULAR, <br /> WHICH WAS REPLACED DUE TO WIRE TO WAS BROKEN AND CAUSING AN L8 SENSOR OUT <br /> ALARM AND NEW SENSOR TESTED GOOD. ONLY ITEMS RELATED TO REPLACEMENT AND <br /> TESTING OF THE L8 ANNULAR SENSOR ARE NOTED ON THIS CERTIFICATION FORM. <br /> Page 5 of 6 <br />