Laserfiche WebLink
LDT 5000 Field Test Apparatus Page 1 of 1 <br /> -�wTanknology Line Leak Detector Test <br /> Work Order: 2384428 Date: 6/13/2025 <br /> Site Name/ID. 7-Eleven#41341 /41341 <br /> Address: 4405 Pacific Ave <br /> City: Stockton State: CA Zip: 95207 <br /> Tank ID T-1 RUL T-2 PUL <br /> Product REG UNLEAD PREMIUM <br /> Product Line 1 1 <br /> Tested From 1 1 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. unreadable unreadable <br /> Pump Operating Pressure(psi) 28.00 28.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI 28.00 28.00 <br /> N/A for Electronic Lo's <br /> Resiliency(ml) 175.00 175.00 <br /> N/A for Electronic Lo's <br /> Metering PSI 19 17 <br /> N/A for Electronic LD's <br /> Opening Time(sec) 3 4 <br /> N/A for Electronic LD's <br /> Test Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Carlos Zaragoza Certification#: 209437 <br /> Technician Signature: Expire Date: 5/28/2027 <br /> Environmental Compliance for Petroleum Systems <br /> ©2025 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />