Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMPIUDC.TEST <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Incon STS <br /> Sump/UDC ID UDC 112 <br /> Sump Manufacturer Bravo <br /> Sump Depth (inches) 30" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) 1220 <br /> Test Start Time 12:16 <br /> Initial Reading 2.1677 <br /> Test End Time 12.31 <br /> Final Reading 2.1676 <br /> Change in Reading 0.0001 <br /> Pass/Fail Criteria 0.002 <br /> [!�iEhtne=ssTest Results ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) m.�. <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked"Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />