Laserfiche WebLink
1115000 Field Test Apparatus Page 1 of 1 <br /> ,,�PTanknoiogy Line Leak Detector Test <br /> Work Order: 2377637 Date: 3/17/2025 <br /> Site Name/ID: 7-Eleven 41531 /41531 <br /> Address: 3379 N Tracy Blvd <br /> City: Tracy State: CA Zip: 95376 <br /> Tank ID RUL PUL. DSL <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 12 12 12 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. N/A N/A N/A <br /> Pump Operating Pressure(psi) 32.00 32.00 38.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 32.00 32.00 38.00 <br /> *N/A for Electronic LD's <br /> Resiliency(ml) 250.00 260.00 250.00 <br /> *N/A for Electronic LD's <br /> Metering PSI 14 14 15 <br /> *N/A for Electronic LD's <br /> Opening Time(sec) 6 6 3 <br /> *N/A for Electronic LD's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: Expire Date: 10/22/2027 <br /> Environmental Compliance for Petroleum Systems <br /> ©2025 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />