My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2025
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
C
>
COUNTRY CLUB
>
1403
>
2300 - Underground Storage Tank Program
>
PR0231995
>
COMPLIANCE INFO_2025
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
4/1/2026 7:36:44 PM
Creation date
1/30/2025 10:21:55 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2025
RECORD_ID
PR0231995
PE
2361 - UST FACILITY
FACILITY_ID
FA0006438
FACILITY_NAME
UNITED #5446
STREET_NUMBER
1403
Direction
W
STREET_NAME
COUNTRY CLUB
STREET_TYPE
BLVD
City
STOCKTON
Zip
95204
APN
12323246
CURRENT_STATUS
Active, billable
QC Status
Approved
Scanner
SJGOV\kblackwell
Supplemental fields
Site Address
1403 W COUNTRY CLUB BLVD STOCKTON 95204
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
115
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
SAN JOAQUIN Environmental Health Department <br /> —COUNTY <br /> Greatness grows here. <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> United #5446 11403 W COUNTRY CLUB BLVD, STOCKTON T1 October 31, 2025 <br /> Item# Remarks <br /> 52 2635(c)(1) 2030036 - Overfill prevention system has not been overridden and meets overfill requirements (TCR 9b) <br /> OBSERVATION: The facility does not have an approved overfill method. <br /> -The required mesh screen on the used oil fill tube was observed in the spill container on the side of the fill tube. <br /> -The remote fill pipe enters the sump below the fill tube shut off valve. <br /> REGULATION GUIDANCE: All underground storage tanks shall be equipped with an overfill prevention system that does <br /> not allow for manual override and meets one of the following requirements: <br /> 1. Alert the transfer operator when the tank is 90 percent full by restricting the flow into the tank or triggering an audible <br /> and visual alarm; or <br /> 2. Restrict delivery of flow to the tank at least 30 minutes before the tank overfills, provided the restriction occurs when <br /> the tank is filled to no more than 95 percent of capacity; and activate an audible alarm at least five minutes before the <br /> tank overfills; or <br /> 3. Provide positive shut-off of flow to the tank when the tank is filled to no more than 95 percent of capacity; or, <br /> 4. Provide positive shut-off of flow to the tank so that none of the fittings located on the top of the tank are exposed to <br /> product due to overfilling. <br /> CORRECTIVE ACTION: Immediately contact a properly licensed, trained, and certified contractor to install an approved <br /> overfill prevention system. Replacement of a mechanical flapper valve requires a permit and inspection by the EHD. If <br /> an external audio/visual alarm is replaced, provide a copy of the service receipt to the EHD. If an approved overfill <br /> prevention system can't be installed immediately, there is a possibility that the used oil UST system may be red tagged to <br /> prevent fuel inputs. <br /> This is a (Class 2)Violation. <br /> Overall Inspection Comments <br /> On site for re-inspection following incomplete testing at the routine Monitoring System Certification on 10/29/25. The <br /> Ronan LS-10 and Ronan LS-3 could not be tested because the technician did not have a certification for the <br /> manufacturer. <br /> The Ronan LS-3 sump sensor and the Ronan LS-10 annular sensor were tested and passed. <br /> All EHD staff time associated with the reinspection will be billed at the current hourly rate ($179). <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting paperwork, <br /> by November 30, 2025. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead of <br /> having them sign. <br /> Starting July 1, 2025, all in-office CERS help will be provided at the EHD hourly rate ($179). To schedule an <br /> appointment, please call (209) 468-3420. <br /> This report was reviewed with Store Manager Panhia Vue on the day of the reinspection. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING THIS <br /> FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: October 31, 2025 Inspector: Inspector Phone: <br /> Printed Name and Title: Lynsey Sammons, REHS (209)616-3067 <br /> Tom Robins, Environmental <br /> Contact <br /> EHD-CUPA Inspection Report IS02 Page 5 of 5 FA0006438 PR0231995 4571375 10/31/2025 <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />
The URL can be used to link to this page
Your browser does not support the video tag.