Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 8. IN-TANK GAUGING TESTING <br /> ❑ Check this box if tank gauging is used only for inventory control. <br /> ❑ Check this box if NO tank gauging equipment is installed. Yes No NA <br /> (Do not complete this section if either box is checked.) <br /> All wiring has been: 1) visually inspected for kinks, breaks and proper entry and ❑✓ ❑ ❑ <br /> termination; and 2) tested for ground faults? <br /> Were all in-tank gauging probes visually inspected for damage and residue buildup ❑✓ ❑ ❑ <br /> to ensure that floats move freely, functionally tested, and confirmed operational? <br /> Was accuracy of system's product level readings tested? ❑✓ ❑ ❑ <br /> Was accuracy of system's water level readings tested? ❑✓ ❑ ❑ <br /> Were all probes reinstalled properly? ❑✓ ❑ ❑ <br /> Were all items on the equipment manufacturer's maintenance checklist completed? ❑✓ ❑ ❑ <br /> Probe ID Probe Model Tanks Monitored Pass Fail <br /> T1 847390-107/628026 UE058U002 Diesel ❑✓ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> 9. COMMENTS <br /> Describe all answers marked "No" or "Fail" and proposed remedy. <br /> List all monitoring equipment either replaced or repaired. <br /> The L3 sensor for the piping sump was tested.The 794380-208 sensor correctly showed "fuel alarm"when introduced into liquid. But <br /> after testing the sensor, it wouldn't come out of"fuel alarm." I wasn't able to get access into the electrical junction box while I was on <br /> site.This sensor needs to be replaced before the sensor will come out of alarm. The monitor is currently showing"13 fuel alarm." <br /> Backup battery voltage reading at 3.70 volts. <br /> Page 5 of 6 <br />