Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2375242 Date: 1/23/2025 <br /> Site Name/ID. TESORO/SPEEDWAY#68151 /43175/4873 <br /> Address: 35 NORTH CHEROKEE LANE <br /> City: LODI State: CA Zip: 95240 <br /> Tank ID 1 2 3 <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 5 5 4 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Red Jacket FX1V Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. UNKNOWN UNKNOWN UNKNOWN <br /> Pump Operating Pressure(psi) 29.00 40.00 42.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 11.00 39.00 29.00 <br /> NIA for Electronic Lo's <br /> Resiliency(ml) 80.00 120.00 135.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 11 25 25 <br /> NIA for Electronic Lo's <br /> Opening Time(sec) 2 3 3 <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass <br /> Technician Comments: Made two 1/3 turn adjustments for 91 LD2000. <br /> Technician Name: Carlos Zaragoza Certification#: 209437 <br /> Technician Signature: Expire Date: 5/28/2027 <br /> Environmental Compliance for Petroleum Systems <br /> ©2025 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />