Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer 0 Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon STS Tester <br /> Sump/UDC ID 87 STP 87 FILL 91 STP 91 FILL <br /> Sump Manufacturer Fiberglass Fiberglass Fiberglass Fiberglass <br /> Sump Depth (inches) 68" 68" 68" 68" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 26" 26" 24" 24" <br /> (inches) <br /> Test Start Time 11:56 am 10:51 am 11:56 am 10:51 am <br /> Initial Reading 4.3294 2.6308 3.8763 3.4748 <br /> Test End Time 12:11 pm 11:06 am 12:11 pm 11:06 am <br /> Final Reading 4.3301 2.6305 3.8773 3.4738 <br /> Change in Reading -0.0007 0.0003 -0.0010 0.0010 <br /> Pass/Fail Criteria 0.0020 0.0020 0.0020 0.0020 <br /> Tightness Test Results p Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail <br /> Sump/UDC ID UDC 1/2 UDC 3/4 UDC 5/6 UDC 7/8 <br /> Sump Manufacturer oPw oPw oPw oPw <br /> Sump Depth (inches) 31" 31" 31" 31" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 18.. 181, 18" 18.. <br /> (inches) <br /> Test Start Time N/A N/A N/A N/A <br /> Initial Reading N/A N/A N/A N/A <br /> Test End Time N/A N/A N/A N/A <br /> Final Reading N/A N/A N/A N/A <br /> Change in Reading N/A N/A N/A N/A <br /> Pass/Fail Criteria 0.0020 0.0020 0.0020 0.0020 <br /> Tightness Test Results ❑ Pass 0 Fail ❑ Pass El Fail ❑ Pass El Fail ❑ Pass 0 Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />