A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> AGS FUEL INC DBA CIRCLE K CHEVRON 1 1490 S MAIN ST MANTECA March 13 2025 <br /> 87 CA Code of Regulations 2060021-Striker plate installed and positioned correctly. ❑OUT ❑R ❑COS <br /> 2631(c),2662(d) <br /> 88 CA Code of Regulations 2060007-Primary and secondary containment designed and constructed to an engineering ❑OUT ❑R ❑COS <br /> 2631(b&d),2666(b&e) specification. <br /> 89 CA Health and Safety 2060008-Enhanced leak detection testing performed before the tank is placed in use ❑OUT ❑R ❑COS <br /> Code 25290.10) <br /> 90 CA Code of Regulations 2060029-SW piping has been upgraded to continuously monitored DW piping when replacement ❑OUT ❑R ❑COS <br /> 2666(b)(2) or repair needed <br /> 91 CA Health and Safety 2010-Administration/Documentation-General ❑OUT ❑R ❑COS <br /> Code 25291(e) <br /> 92 2015-Administrative/Documentation-General Local Ordinance ❑OUT ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 10 CA Code of Regulations 2638(c), 2638(d)2030074-Annual Monitoring System Certification Form to the CUPA within <br /> 30 days of completion of the test. <br /> OBSERVATION:A monitoring system certification and leak detector testing was performed on 3/22/2024. A test <br /> report has not been submitted to the EHD or the California Environmental Reporting System (CERS). <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the test. <br /> CORRECTIVE ACTION: Immediately provide this report to the EHD. <br /> This is (Minor)Violation. <br /> 35 CA Health and Safety Code 25290.1(e)2030065- Interstitial space of the UST is under constant VPH monitoring (TCR <br /> 9d). <br /> OBSERVATION:The 304 sensor on the 5/6 dispenser sensor failed when tested. <br /> REGULATION GUIDANCE:The interstitial space of the UST shall be maintained, as designed, under constant vacuum <br /> or pressure such that a breach in the primary or secondary containment is detected before the hazardous substance <br /> is released into the environment. <br /> CORRECTIVE ACTION: The sensor was replaced and retested during the inspection. <br /> This was corrected on site. <br /> This is a repeat violation (Class 2) Violation. <br /> 47 CA Health and Safety Code 25290.1(c3), 25290.2(c3)2030008-Secondary containment installed after July 1, 2003 is <br /> free of water. <br /> OBSERVATION: Liquid was found in the 91 STP sump, diesel STP sump and 87 STP sump. <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION: The service technician removed of liquid from the[GRADE/LOCATION]sump and returned the <br /> sensor to its proper location. Immediately contact a properly licensed,trained, and certified contractor to address the <br /> water intrusion into the 91 STP sump, diesel STP sump and 87 STP sump sump under permit and inspection of the <br /> EHD. <br /> FA0023750 PR0541436 SCO01 03/13/2025 <br /> EHD Rev.12/06/2021 Page 5 of 6 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />