Laserfiche WebLink
LDT 5000 Field Test Apparatus Page 1 of 1 <br /> ,,�PTanknoiogy Line Leak Detector Test <br /> Work Order: 2379669 Date: 5/28/2025 <br /> Site Name/ID: 7-ELEVEN 41342/41342 <br /> Address: 1233 E Dr. Martin Luther King Jr Blvd <br /> City: Stockton State: CA Zip: 95205 <br /> Tank ID T-1 RUL T-2 PUL Diesel <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 11 11 11 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. unreadable unreadable 21071525 <br /> Pump Operating Pressure(psi) 30.00 32.00 33.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 30.00 30.00 31.00 <br /> *N/A for Electronic LD's <br /> Resiliency(ml) 200.00 225.00 200.00 <br /> *N/A for Electronic LD's <br /> Metering PSI 16 17 18 <br /> *N/A for Electronic LD's <br /> Opening Time(sec) 4 6 6 <br /> *N/A for Electronic LD's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: Expire Date: 10/22/2027 <br /> Environmental Compliance for Petroleum Systems <br /> ©2025 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />