My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2025
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
L
>
LOUISE
>
2551
>
2300 - Underground Storage Tank Program
>
PR0231659
>
COMPLIANCE INFO_2025
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
2/27/2026 7:52:56 PM
Creation date
3/3/2025 4:48:59 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2025
RECORD_ID
PR0231659
PE
2361 - UST FACILITY
FACILITY_ID
FA0003849
FACILITY_NAME
Verizon Business: MANTECA
STREET_NUMBER
2551
Direction
E
STREET_NAME
LOUISE
STREET_TYPE
AVE
City
MANTECA
Zip
95336
APN
19801005
CURRENT_STATUS
Active, billable
QC Status
Approved
Scanner
SJGOV\kblackwell
Supplemental fields
Site Address
2551 E LOUISE AVE MANTECA 95336
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
46
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Verizon Business: MANTECA 2551 E LOUISE AVE, MANTECA Aril 15 2025 <br /> 87 CA Code of Regulations 2060021-Striker plate installed and positioned correctly. ❑OUT ❑R ❑COS <br /> 2631(c),2662(d) <br /> 88 CA Code of Regulations 2060007-Primary and secondary containment designed and constructed to an engineering ❑OUT ❑R ❑COS <br /> 2631(b&d),2666(b&e) specification. <br /> 89 CA Health and Safety 2060008-Enhanced leak detection testing performed before the tank is placed in use ❑OUT ❑R ❑COS <br /> Code 25290.10) <br /> 90 CA Code of Regulations 2060029-SW piping has been upgraded to continuously monitored DW piping when replacement ❑OUT ❑R ❑COS <br /> 2666(b)(2) or repair needed <br /> 91 CA Health and Safety 2010-Administration/Documentation-General ❑OUT ❑R ❑COS <br /> Code 25291(e) <br /> 92 2015-Administrative/Documentation-General Local Ordinance ❑OUT ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 2 CA Code of Regulations 2711 2010010 -Complete and accurate UST Operating Permit Application has been <br /> submitted.. <br /> OBSERVATION: UST Tank Information forms are not current in the California Environmental Reporting System <br /> (CERS). <br /> -The tank forms list vent piping as fiberglass primary and fiberglass secondary. Vent piping was observed as flex <br /> piping for primary and secondary during the inspection. <br /> REGULATION GUIDANCE:Any change of information must be updated in CERS within 30 days of the changes. <br /> CORRECTIVE ACTION: Immediately log into CERS, update the required information, and submit for review by the <br /> EHD. <br /> This is (Minor)Violation. <br /> 56 CA Code of Regulations 2716(a-e)2030013-DO inspections completed at least every 30 days and meet all <br /> requirements(TCR 12). <br /> OBSERVATION:The owner/operator failed to respond in Section 5 to compliance issues listed in Section 3 by the <br /> designated operator. Multiple designated operator reports listed compliance issues in Section 3 and owner/operator <br /> did not describe corrective actions that will be taken regarding the listed compliance issues. <br /> REGULATION GUIDANCE:2716(e)Within 72 hours of being provided a signed copy of the"Designated Underground <br /> Storage Tank Operator Visual Inspection Report,"the owner or operator shall: (1)Provide a description of each <br /> corrective action taken or to be taken for any compliance issues discovered during the inspection on the copy of the <br /> "Designated Underground Storage Tank Operator Visual Inspection Report"signed by the designated UST operator; <br /> and (2)Sign and date the report, acknowledging the results of the inspection. <br /> CORRECTIVE ACTION: Ensure that corrective actions to be taken or will be taken for compliance issues are <br /> described in Section 5 of the designated operator reports. <br /> This is a repeat violation (Class 2) Violation. <br /> 58 CA Code of Regulations 2715(c)(3), 2715(c)(4)2010015- Copies of Facility Employee Training Certificates maintained. <br /> OBSERVATION: The Facility Employee Training Certificate for 2024 incorrectly listed the initial training date as the <br /> date of training.The initial date of training is not the same date as the date of training on the bottom of the form. Initial <br /> training dates do not change. <br /> FA0003849 PR0231659 SCO01 04/15/2025 <br /> EHD Rev.12/06/2021 Page 5 of 6 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />
The URL can be used to link to this page
Your browser does not support the video tag.