Laserfiche WebLink
E.O. VR-204 <br /> Veeder-Root In-Station Diagnostics Balance Vapor Flow Meter Operability Test Procedure <br /> Permit Number:N-633 DATE 6/13/25 Test Company:NOR-CAL TANK TESTING <br /> Site Name: PERSHING GAS FOR LESS Technician:DAVID WINKLER <br /> Site Address: 4445 N PERSHING Certification Number Expiration Date <br /> City: STOCKTON CA District: SJV 0082 3/31/26 <br /> V ST: 0774 10/16/24 <br /> Veeder-Root: B34975 7/20/24 <br /> Flow ISD Flow Meter Gas Flow Meter <br /> Meter Fueling Converted %Diff. Pass/ <br /> Serial Point Start Stop Diff.(in gal) Start Stop Diff.(in cf) Diff. in al) Fail <br /> 79055 1/2 16854.025 16861.586 7.561 8080 8180 100 7.481 1.0 Pass <br /> 79046 3/4 36254.085 36261.676 7.591 8180 8280 100 7.481 1.4 Pass <br /> 79106 5/6 78521.595 78528.988 7.394 8280 8380 100 7.481 .6 Pass <br /> 79108 7/8 14141.258 14148.739 7.481 8380 8480 100 7.481 0 Pass <br /> o ISD_Differencegallans —Gas_Flow_Meter_Differenceganons <br /> Gallons =Cubic—Feet x 7.481 /oDifference= x 100 <br /> Gas_Flow_Meter_Differencegarrons <br /> I declare, under penalty of perjury under the laws of the state of California that based on information and belief formed after reasonable inquiry, the <br /> statements and information provided in this document are true, accurate, and complete. <br /> Signature of Technician: _ Date: 6/13/25 <br /> Ver. 1.3—08.07.09 <br />