Laserfiche WebLink
The following is an itemized list of CP22 - UST FULL violations that have not been <br /> addressed for PERSHING GAS FOR LESS as of October 03, 2025. <br /> Open violations from April 22, 2025 Inspection <br /> Violation#59-2030001 -Records of release detection monitoring and maintenance properly maintained <br /> (TCR 9d). <br /> OBSERVATION: Maintenance and monitoring records for the last three years were not found on site <br /> Documented response to the following alarms: <br /> -7/18/24 L5(diesel annular)low liquid alarm <br /> -8/1/24 Q1 (91 LLD)gross line fail alamn <br /> REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1)date and time of all monitoring or sampling; (2)monitoring equipment calibration and maintenance records; <br /> (3)results of any visual observations; (4)results of sample analysis performed a lab or in the field; (5) logs of all <br /> readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6)results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the last <br /> three years on site. Submit copies of any missing work orders and alarm records to the EHD. <br /> 13 This violation was corrected ❑This violation will be corrected by(date): <br /> I] Supporting documents included l <br /> Describe actions taken or will be taken to correct violation: ��� L u I L( 1fC-C� P lH/lr� � <br /> Page 3 of 3 <br />