Laserfiche WebLink
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> 7-ELEVEN INC#41530 1 1110 N MAIN ST MANTECA May 19 2025 <br /> 87 CA Code of Regulations 2060021-Striker plate installed and positioned correctly. ❑OUT ❑R ❑COS <br /> 2631(c),2662(d) <br /> 88 CA Code of Regulations 2060007-Primary and secondary containment designed and constructed to an engineering ❑OUT ❑R ❑COS <br /> 2631(b&d),2666(b&e) specification. <br /> 89 CA Health and Safety 2060008-Enhanced leak detection testing performed before the tank is placed in use ❑OUT ❑R ❑COS <br /> Code 25290.10) <br /> 90 CA Code of Regulations 2060029-SW piping has been upgraded to continuously monitored DW piping when replacement D OUT ❑R ❑COS <br /> 2666(b)(2) or repair needed <br /> 91 CA Health and Safety 2010-Administration/Documentation-General ❑OUT ❑R ❑COS <br /> Code 25291(e) <br /> 92 2015-Administrative/Documentation-General Local Ordinance ❑OUT ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 14 CA Code of Regulations 2637.2(d&e), 2665(a&b)2010018-Overfill prevention equipment inspection report form <br /> submitted to the UPA within 30 days. <br /> OBSERVATION:An overfill prevention equipment inspection was performed on 05/17/13. A test report has not been <br /> submitted to the EHD or the California Environmental Reporting System (CERS). <br /> REGULATION GUIDANCE:A copy of the inspection report form must be submitted within 30 days of the test. <br /> CORRECTIVE ACTION: Copy of overfill testing was sent to EHD. <br /> This is (Minor)Violation. <br /> 50 CA Code of Regulations 2635, 2637.1, 2665, 2712 2060020-Spill buckets meet requirements, have been tested as <br /> required, and records kept for 36 mths(TCR 9a). <br /> OBSERVATION:The 87 spill container failed when tested. <br /> REGULATION GUIDANCE:All spill containers shall have a minimum capacity of five gallons and be capable of <br /> containing a spill or overfill until it is detected or cleaned up. <br /> CORRECTIVE ACTION: Immediately contact a properly licensed,trained, and certified contractor to repair or replace <br /> the spill container under permit and inspection of the EHD. <br /> This is(Class 2)Violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by June 18, 2025. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead of <br /> having them sign. <br /> Starting July 1, 2024, all in-office CERS help will be provided at EHD hourly rate ($172). <br /> To schedule an appointment, please call (209)468-3420. <br /> FA0000794 PR0547874 SCO01 05/19/2025 <br /> EHD Rev.12/06/2021 Page 5 of 6 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />