Laserfiche WebLink
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> AXIS-MSO LLC#6822 2132 MARIPOSA RD STOCKTON Aril 16 2025 <br /> 87 CA Code of Regulations 2060021-Striker plate installed and positioned correctly. ❑OUT ❑R ❑COS <br /> 2631(c),2662(d) <br /> 88 CA Code of Regulations 2060007-Primary and secondary containment designed and constructed to an engineering ❑OUT ❑R ❑COS <br /> 2631(b&d),2666(b&e) specification. <br /> 89 CA Health and Safety 2060008-Enhanced leak detection testing performed before the tank is placed in use ❑OUT ❑R ❑COS <br /> Code 25290.10) <br /> 90 CA Code of Regulations 2060029-SW piping has been upgraded to continuously monitored DW piping when replacement ❑OUT ❑R ❑COS <br /> 2666(b)(2) or repair needed <br /> 91 Eod252 <br /> d Safety 2010-Administration/Documentation-General ❑OUT ❑R ❑COS <br /> e) <br /> 92 2015-Administrative/Documentation-General Local Ordinance ❑OUT ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 53 CA Health and Safety Code 25292.2; CCR 2711(a)(11)2010007-Submitted/maintained current Cert of Financial <br /> Responsibility/mech of financial assurance(TCR 11). <br /> OBSERVATION: Current financial responsibility documents were not found on site.The most recent financial <br /> responsibility documents observed on site were dated 11/3/2023. <br /> REGULATION GUIDANCE:A copy of current financial responsibility documents are required to be maintained on site. <br /> CORRECTIVE ACTION: Immediately obtain a copy of the facility's financial responsibility documents and maintain a <br /> copy on site. <br /> This is (Minor)Violation. <br /> 59 CA Code of Regulations 2712(b)(1-2)2030001 - Records of release detection monitoring and maintenance properly <br /> maintained (TCR 9d). <br /> OBSERVATION: Maintenance and monitoring records for the last three years were not found on site.The following <br /> records were not observed on site: <br /> -4/17/2024 monitoring system certification and spill container test results <br /> -4/5/2022 monitoring system certification and spill container test results <br /> -5/11/2022 secondary containment test results <br /> -4/17/2024 overfill prevention equipment test results <br /> REGULATION GUIDANCE:These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1)date and time of all monitoring or sampling; (2)monitoring equipment calibration and maintenance records; <br /> (3)results of any visual observations; (4)results of sample analysis performed a lab or in the field; (5)logs of all <br /> readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6)results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the last <br /> three years on site. Submit copies of any missing work orders and alarm records to the EHD. <br /> This is(Minor)Violation. <br /> 69 CA Code of Regulations 2712(i)2030033-A current UST monitoring plan has been submitted and is readily <br /> accessible at the facility. <br /> OBSERVATION:An approved copy of the monitoring plans were not available for inspection.The monitoring plan <br /> observed on site is outdated. It still lists Ronan L-3 annular sensors for the 87, 91 and diesel tanks. <br /> FA0001480 PR0231669 SCO01 04/16/2025 <br /> EHD Rev.12/06/2021 Page 5 of 6 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />