Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 5. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Tank ID (one OPE per column) 87 97 91 <br /> Are both vent and tank riser piping f Yes f Yes f Yes Yes <br /> secondarily contained? No No No No <br /> OPE Model OPw OPW ❑pw <br /> What is the OPE response when activated? f Shut off f Shut off y/1 Shut off Shut off <br /> (Check all that apply.) Flow Flow Flow Flow <br /> Restricts Restricts Restricts Restricts <br /> Flow Flow Flow Flow <br /> Audible Audible Audible Audible <br /> Alarm Alarm Alarm Alarm <br /> iDVisual Visual 17 Visual Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent piping Yes* Yes* Yes* Yes* <br /> that may interfere with the OPE operation? f N❑ f No f No No <br /> At what level in the tank is the OPE set to <br /> activate? (Inches from bottom of tank) 8112 76.125" 76.675" <br /> What is the percent capacity of the tank at 93% 89% 89% <br /> which the OPE activates? <br /> Is the OPE in proper operating condition to f Yes f�Yes f Yes Yes <br /> respond when the stored substance No No No No <br /> reaches the designated regulatory level? <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results f pass ,/ Pass ,/ Pass Pass <br /> Fail Fail Lj Fail HFail <br /> 8. COMMENTS <br /> Describe all results marked "Fail'and each proposed remedy. <br /> * Mark here if: <br /> Flow restrictors interfere with overfill prevention and equipment repairs required. <br /> Additional copies of this page may be attached. <br /> Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s) <br /> Page 2 of 2 <br />